Operating Manual
49
•
Level SOC 1 active {1439} {1442}
•
Level SOC 1 {1440} {1443}
•
Duration 1 {1581} {1590}
•
Level SOC 2 active {1582} {1591}
•
Level SOC 2 {1583} {1592}
•
Duration 2 {1584} {1593}
•
Level SOC 3 active {1585} {1594}
•
Level SOC 3 {1586} {1595}
•
Duration 3 {1587} {1596}
•
Level SOC to deactivate the auxiliary contact {1441} {1444}
•
Duration on level for deactivation {1588} {1597}
•
Deactivate if the battery is in floating phase {1589} {1598}
8.1.1.10 Security : Limit the time of activation {1512} {1513}
Caution :
If the maximum duration for the relay activation that you have selected is
reached and if the activation conditions are still present (for instance a
battery undervoltage), the contact will not be reactivated as long as the
conditions are present. Therefore there is a risk that the auxiliary contact
remains locked in this deactivated state and you will have to reset manually
this alarm by deactivating and then activating this parameter.
Use this function with care and only as a security.
8.1.1.11
Maximum duration of activation {1514} {1515}
When the conditions are met, either one or two relays are activated permanently. If
you wish that the activation duration is limited in time, even if the conditions are met,
you can activate this function. Once the relay is activated, a countdown runs
according to the duration you have selected. Once this countdown is completed the
relay is released, even if the conditions are still there. The relay can not be anymore
activated as long as the activation conditions have not disap-peared.
8.1.1.12 Reset all settings {1569} {1570}
This function serves to reset all previous settings done on the corresponding auxiliary
contact. Once this operation done, the auxiliary contact is not activated anymore.
Caution: this function cannot be cancelled.
Use this function before programming any function for an auxiliary contact.
By doing this way you are sure that you begin with no unexpected setting
who can activate the contact.
8.1.2
AUXILIARY CONTACTS 1 AND 2 EXTENDED FUNCT. {1489}
8.1.2.1 Generator startup
The two contacts may be combined in order to automatically start up a generator
equiped with an electric starter. In this case the two contacts are dedicated to this
function.
Auxiliary contact 1 serves as an operational contact and auxiliary contact 2 as a
startup contact.
Содержание iUPS101
Страница 1: ...Installation Operating Manual iUPS101...
Страница 55: ...Operating Manual 55...
Страница 59: ...Operating Manual 59 11 5System Assembly Details...
Страница 62: ...Operating Manual 62 14 Certification 14 1Atex Label...
Страница 63: ...Operating Manual 63 14 2Atex Certificate...
Страница 64: ...Operating Manual 64...
Страница 65: ...Operating Manual 65...
Страница 66: ...Operating Manual 66...
Страница 67: ...Operating Manual 67...
Страница 68: ...Operating Manual 68 14 3iUPS101 EC Declaration of Conformity...
Страница 69: ...Operating Manual 69 14 4UPS System EC Declaration of Conformity...