FIGURE 46
Connecting the grounding terminal
1.
Grounding terminal
NOTE
The grounding lug must be sized according to NEC/CEC requirements. A typical installation would require:
1. Lug, copper, suitable wire size, #10 2-hole, 5/8" centers. For #10 ga. Wire, example lugs are:
•
Panduit LCD10-10AF-L
•
Pencom EL1244
•
Hardware Specialties 912302
2. Screw, 10-32, ½", qty 2
3. Washer, #10, external locking, qty 2
Perform the following steps to connect to the grounding terminal.
1. Ensure that the rack in which the SLX 9030/9030-T device is mounted is properly grounded and in compliance with local
regulations.
2. Ensure that there is a good electrical connection to the grounding point on the rack (no paint or isolating surface treatment).
3. Crimp the included grounding lug to a grounding wire of at least 12 American Wire Gauge (AWG). The 12 AWG wire and
grounding lug should be crimped together using a proper tool.
4. Attach the 12 AWG stranded copper wire to the grounding terminal on the SLX 9030/9030-T device using the screws
included in the grounding kit.
5. Attach the grounding wire to a grounding point.
NOTE
The terminal for the connection of a grounding conductor is not to be used with an aluminum conductor.
Grounding the SLX 9030/9030-T device
ExtremeSwitching SLX 9030 Hardware Installation Guide
90
9035691-02 Rev AD
Содержание EN-SLX-9030-48S-4C
Страница 6: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 6 9035691 02 Rev AD...
Страница 10: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 10 9035691 02 Rev AD...
Страница 64: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 64 9035691 02 Rev AD...
Страница 76: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 76 9035691 02 Rev AD...
Страница 82: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 82 9035691 02 Rev AD...
Страница 96: ...ExtremeSwitching SLX 9030 Hardware Installation Guide 96 9035691 02 Rev AD...