Working Principles of ESC-200P
Data transfer protocol is called DC Power Line Communication
- The information runs in the same cable with the voltage
The Center is constantly checking the lights operating status
- The first error doesn
’
t show up on the display. The Error Code shows up only if
the same light/address gives the error ten (10) times.
o
This is how we can reduce failures coming from other networks.
o
There are no external signs about the Center checking the operating
status.
- How long does it take to Error Code to show up on Centers display depends on
how many lights you have in the system and how they are installed.
- Checking the LEDs makes the Emergency light blink briefly about once a
day.
The ESC-200P Center makes the battery test every month.
- The Center makes the luminaires to work with batteries during the test. The
voltage (65VDC) still remains in the line.
- The test lasts for 30 minutes and the Emergency lights light up during the
test.
- The automatic testing cannot be turned off.