![Exit Light ESC-200P Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/exit-light/esc-200p/esc-200p_manual_2450794002.webp)
Hermiankatu 6–8, 33720 Tampere | +358 10 773 5400 | [email protected] |
MANUAL
Quick Start
1. Install the panel using mounting holes.
2. After luminaires are installed (please note that the luminaires are suited for ESC-200P
system), connect cables of loops to central panels.
•
Panel has 10, 16 and 24 sections for addressable luminaires. These are divided into
two loops (L1 and L2), half-by-half: 5 + 5, 8 + 8 and 12 + 12.
•
In section could be mixed with emergency lights and exit lights.
•
Maximum 20 luminaires can be attached on one section, in total 200 luminaires per one
panel.
•
Do not connect luminaires with live voltage on panels!
•
Make sure that +, - and G markings are connected right way around.
3. Panel has three (3) outputs for 230V emergency lights. Do not under any circumstance
connect addressable LED emergency lights to these outputs. Outputs are only applicable to
be used for 230V emergency lights.
4. Connect the small NiMH battery to panel printed circuit board and 12 V backup batteries to
panels battery cables. Backup batteries of panels have a voltage of 12 V.
5. Connect power to central panel power supply.
6. From control panel, choose ”INVERTER USE” and choose either ”ON + BATT. CHECK” to
operate as central battery system and to have monitoring for both batteries and inverter.
”ON + BATT.CHECK” is default mode of ESC-200P panel.
7. Press the MENU-button and go to ”START NEW INSTALLATION”. You can scroll the menu
with UP and DOWN buttons. New commissioning is started by pressin MENU-button. On
display there is a note “INSTALLATION IN PROGRES” and ”TIME ABOUT 30 MIN”. Panel
writes to its memory found luminaires from each line. Luminaire inventory can be scrolled
with LEFT and RIGHT buttons. After commissioning has been executed panel returns to a
normal state.
Control panel has two lines for luminaires. Maximum capacity of lines are 100
luminaires per loop, 200 luminaires per one panel.
8. When panel has found all luminaires in loops, “EVERYTHING OK” is appeared on display.