Controlling 230V emergency lights with external
control
Three (3) 230V emergency light outputs can be turned on with dry contact by connecting inverter to
external control according to picture 9.
Picture 9: 230V emergency light outputs control
ESC-200P design and cabling principles
In order for the proper functioning of system, please use following design and cabling principles:
•
Always use shielded FRHF-cable.
•
Keep lines as short as possible (maximum distance around 300 m).
•
Maximum number of 100 luminaires per line.
•
Place the luminaires to lines with as even spacing as possible.
•
If long spans are needed, prepare own line for it and do not include any other luminaires on
the way.
•
Cable crimping should be kept to a minimum on luminaires and switch boxes.
•
In luminaire connections take care that positive and negative connections are connected
right way around. Also take care to connect earth conductor.
•
2 Area Monitoring Units(AMUSs) is comparable to one luminare. So if you have 80
luminaires on line, maximum AMUs is 40 per line. (max100 luminare per line)
•
If Area Monitoring Units (AMUs) are being used, ensure that between AMUs and controlled
luminaires there are more than 5 meters of cable to ensure proper communication.
For example AMU
can be used.