To configure these parameters through the SSE232-LE Web Page:
Select the “COM A” link from the menu.
Enter the values as necessary.
Click on the “Send” button, so the SSE232-LE may take the changes.
You may use the configuration command console to change these parameters. In the commands
that allow to change these parameters you must indicate the COM you are referring to.
Table 9 - Server Mode Channel Configuration
Command
Description
MODEx:(S|C)
Configures the COM x mode. To select Server Mode, select S.
PORTx:(1..65535)
Port in which the client’s connection is waited.
INACTOUTx:(0..10000)
Maximum time of inactivity allowed to the connection corresponding to the COM x, after
which the connection is terminated and the device returns to client waiting mode. It is
expressed in minutes.
3.2.6 Client Mode Channel Configuration
In Client Mode, each channel tries to connect to a specified server (IP-Port) every 10 seconds.
Once the connection established, the information of the socket is transparently transmitted by the
corresponding COM and vice versa.
These are the configuration parameters for that channel in client mode:
Mode: The channel mode must be configured as Client.
Port: Client channel Port.
Server IP: IP address of the server to which the client’s channel will connect.
Server Port: Server Port of the server to which the client’s channel will connect.