Instruction manual for POWERLINE RT 1-3 kVA UPS units
45
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2016-07-13 12:09
PARAMETERS \ TYPE
POWERLINE RT
POWERLINE RT 1000
POWERLINE RT 2000
POWERLINE RT 3000
BATTERIES AND BACKUP TIMES
Internal batteries
12 V / 9 Ah VRLA
12 V / 9 Ah VRLA
Total number of internal batteries
1 x 3
1 x 6
Maximum permissible combined capacity of
internal battery pack
9 Ah
External battery packs
Yes
Maximum number of battery packs
4
Backup time using internal battery pack (100% /
80% / 50% of Pmax)
8 / 12 /20 min.
8 / 12 / 20 min.
3 / 6 / 12 min.
Backup time using internal bat battery
pack (100% / 80% / 50% of Pmax)
26 / 37 /78 min.
26 / 37 / 78 min.
20 / 28 / 41 min.
Rated voltage for the DC circuit
36 V DC
72 V DC
Maximum charging time for UPS internal
batteries - after batteries have been 80%
discharged
≤ 4 h
Charging current, maximum
1.2 A
MECHANICAL PARAMETERS
Dimensions (height. x width x depth)
86 (2U) x 438 x 482 mm
86 (2U) x 438 x 658 mm
Weight
7)
18.5 kg
30.5 kg
31 kg
Weight for transporting (gross)
7)
22 kg
35 kg
36 kg
Dimensions for transporting (height. x width x
depth)
245 x 530 x 625 mm
230 x 585 x 880 mm
Position in transit
Horizontal
PROTECTIONS AND SAFEGUARDS
Input protection
Short circuit protection -
Automatic fuse
10 A / 250V AC
Short circuit protection -
Automatic fuse
12 A / 250V AC
Short circuit protection -
Automatic fuse
16 A / 250V AC
Against overvoltage (Anti-surge)
Output protection
Inverter-based operation
– electronic short-circuit protection and overload
protection
FEATURES AND ADDITIONAL FUNCTIONS
UPS power supply connection
1 x IEC 320 C14 (10 A)
1 x IEC 320 C20 (16 A)
Output connections (socket type and quantity)
3 x IEC 320 C13 (10A) controlled (2 groups)
3 x IEC 320 C13 (10A) non-controlled
3 x IEC 320 C13 (10A)
controlled (2 groups)
3 x IEC 320 C13 (10A)
non-controlled
1 x IEC 320 C19 (16A)
EPO / ROO
Yes (NC) / Yes
Signaling
Acoustic and visual; LCD display; LEDs
Communication interface
RS232, USB, Port RJ11
– detection of battery packs,
network management card SNMP / HTTP
– optional,
AS 400 card with volt-free contacts - optional
Monitoring and management software
PowerSoft Professional
GREENPOWER operating threshold
8)
< 45 W
STANDARDS APPLIED
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Caution: The manufacturer reserves the right to change the above listed parameters without notice.
ADDITIONAL NOTES:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load
current.
2)
The Rack Kit is optional.
3)
With internal batteries 5 ÷ 35°C. Constant exposure of the device to environment temperature over +25°C results in reducing
battery life.
4)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.
5)
Can be configured by software and LCD display. The output power is reduced by 20% for rated output voltage of 200 V. The
output power is reduced by 10% or rated output voltage 208 V.
6)
With prolonged operation with recommended load.
7)
Weight for the typical battery.
8)
In battery mode with no load or load less than threshold value, UPS turn off automatically after 5 minutes.
Содержание POWERLINE RT 1000