MENU AND FUNCTIONS
Functions available in the menu and submenu are described below.
DISPLAY PANEL
Function
Displays current operation mode, information about warnings and errors
MENU 1.- STATUS
Function
Displays input and output values (voltage, frequency, load...)
MENU 2.- EVENTS
Function
Displays five most recent events (errors, warnings...)
1
EPO RELEASE
UPS stopped working, because EPO was activated (remote power supply off)
2
BAT. ERROR
Battery error detected
3
INVERTER
OVERLOAD
Inverter overload detected (mains or backup mode)
4
BYPASS
OVERLOAD
Overload detected when the device is in the bypass mode.
5
FAN ERROR
Fan error detected
6
CHARGER
VOLT. TOO HIGH
The charger supplies too high voltage (internal error)
7
DC BUS
VOLT. TOO HIGH
DC voltage in the DC bus is too high (internal error)
8
DC BUS
VOLT. TOO LOW
DC voltage in the DC bus is too low (internal error)
9
DC BUS
UNSTABLE
DC voltage in the DC bus is unstable (internal error)
10
INVERTER
VOLT. TOO HIGH
The inverter supplies too high voltage (internal error)
11
INVERTER
VOLT. TOO LOW
The inverter supplies too low voltage (internal error)
12
INVERTER
SHORT CIRCUIT
Inverter short circuit (internal error)
13
PHASE ERROR
CHECK AC INPUT
14
OVERHEATING
Device overheating
15
NO EVENTS
No events in the register
The LCD displays shows five most recent events. They are numbered from 1 to 5, where 1 is
most recent, and 5 oldest event. Event 1 is displayed as first, and events from 2 to 5 are
displayed when the forward button is pushed. After displaying the event type, the next screen
tells you when it occurred relative to the device's working time. This is not a calendar date.
The time follows the format: DDDD:HH:MM:SS, where DDDD is the consecutive day of the
device's work, HH
– hours, MM – minutes, SS – seconds. The next screen is the next event.