Fig. 9. Installation of the UPS with a battery pack
ELECTRICAL SYSTEM
The mains socket the UPS is to be connected to should be located near the battery
and should be easily accessible.
No extension cords should be used for connecting the UPS unit.
CAUTION!
The UPS is disconnected from the mains only when the
power lead is removed from the mains socket.
Due to the type and placement of the fuses in the power supply unit, the protection
systems in the building's electric system are used as one of the protection levels.
This is necessary to ensure short circuit protection of the power supply unit.
The parameters of the building's electric wiring system protection should be selected
to meet the requirements of the load connected to the wiring system and the type the
load. In extreme cases, different characteristics of the building’s and the UPS unit’s
electrical protection systems may result in the former system being activated earlier.