EVCO S.p.A.
Vcolor 679/689
| Installer manual ver. 1.0 | Code 144VC679I104
page 56 of 70
A16
0
900
sec
300
buzzer reactivation time if alarm(s) still active
0 = not enabled
A17
0
1
- - - -
0
alarm output activation
0 = with alarm active
1 = with alarm not active
Par.
Min
Max
Unit
Default Evaporator and condenser fan
F0
0
1
- - - -
0
evaporator fan activity during the blocking phase
0 = parallel function with the compressor
1 = continuous function
F1
0
1
- - - -
0
evaporator fan activity during the holding, cooling and pre-
cooling phases
0 = parallel function with the compressor
1 = continuous function
F2
0
1
- - - -
0
evaporator fan activity during the re-awakening phase
0 = parallel function with the main loads
1 = continuous function
F3
0
1
- - - -
0
evaporator fan activity during the proofing phase
0 = parallel function with the main loads
1 = continuous function
F4
0
1
- - - -
0
evaporator fan activity during the baking delay phase
0 = parallel function with the main loads
1 = continuous function
F5
0
1
- - - -
0
evaporator fan activity during the heating phase
0 = parallel function with the main loads
1 = continuous function
F10
1
10
- - - -
10
fan speed during the pre-cooling phase
F11
1
10
- - - -
10
fan speed during the dehumidification phase
F12
0
15
min
2
fan stop after the dripping phase
F13
0
250
s
0
evaporator fan switch-off delay from main load switch-off
F14
1
600
s
0
evaporator fan cycle time
if=0, cyclical fan switch-on will be deactivated
F15
1
600
s
0
evaporator fan switch-on time within the F14 cycle time
F16
0.0
99.0
°C
20.0
condenser fan threshold
(if condenser probe is configured)
F17
0
240
s
5
condenser fan switch-off delay from compressor switch-off
(if condenser probe is disabled)
F18
0
3
- - - -
2
condenser fan activation mode (if condenser probe is
configured)
0 = temperature adjusted (with compressor ON or OFF)
1 = temperature adjusted only if compressor is OFF (on if
compressor is ON)
2 = temperature adjusted only if compressor is ON (OFF if
compressor is OFF)
3 = temperature adjusted if compressor is OFF, OFF
during defrost
F19
0
240
s
15
evaporator fan switch-on delay from when the door is closed,
or the door switch input is deactivated
F21
1
10
- - - -
8
evaporator fan start-up speed
F22
1
240
s
5
start-up time when the evaporator fan is switched on
F23
0
100
%
35
evaporator fan min. speed calibration value
F24
0
100
%
65
evaporator fan max. speed calibration value
F25
-50.0
99.0
°C
1.0
evaporator temperature below which the evaporator fan is