8.4
Pre- cooling cycle (for retarding-proofing only)
A pre-cooling cycle can be activated in the chamber while waiting for the retarding-proofing cycle to be selected.
Pressing the pre-cooling key opens up a screen where the cabinet temperature setpoint and the speed of the evaporator fan can be set.
The function is started up by pressing the START key.
When the cycle has been activated, the controller automatically goes to the main page and displays the cabinet temperature and the
setpoint to reach in the place of the pre-cooling key.
When it reaches the temperature setpoint for the first time, the buzzer will sound. If the temperature in the cabinet is equal to or lower
than the setpoint, the pre-cooling function cannot be activated.
The pre-cooling function is of infinite duration and ends as soon as a retarding-proofing, cooling or heating cycle is started up. To
manually terminate the pre-cooling cycle, press the blue key showing the temperature.