
Operating Instructions
Safety System MGBS-P-L.-AP…
20
(translation of the original operating instructions) 2527245-02-01/22
11. Electrical connection
WARNING
In the event of a fault, loss of the safety function due to incorrect connection.
Ì
To ensure safety, both safety outputs
(FO1A and FO1B) must always be evaluated.
Ì
Monitoring outputs must not be used as safety outputs.
Ì
Lay the connecting cables with protection to prevent the risk of short circuits.
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connection.
Ì
The power supply for the evaluation electronics is isolated from the power supply for the guard
locking solenoid.
Ì
The device generates its own test pulses on the output lines FO1A/FO1B. A downstream
control system must tolerate these test pulses, which may have a length of up to 0.35 ms.
Depending on the inertia of the downstream device (control system, relay, etc.), this can lead to
short switching processes.
Ì
The inputs on an evaluation unit connected must be positive-switching, as the two outputs on the
safety switch deliver a level of +24 V in the switched-on state.
Ì
All the electrical connections must either be isolated from the mains supply by a safety transformer
according to IEC 61558-2-6 with limited output voltage in the event of a fault, or by other equivalent
insulation measures (PELV).
Ì
All electrical outputs must have an adequate protective circuit for inductive loads. The outputs must
be protected with a free-wheeling diode for this purpose. RC interference suppression units must
not be used.
Ì
Power devices which are a powerful source of interference must be installed in a separate location
away from the input and output circuits for signal processing. The cable routing for safety circuits
should be as far away as possible from the cables of the power circuits.
Ì
To avoid EMC interference, the physical environmental and operating conditions at the installation
site of the device must comply with the requirements according to the standard EN 60204-1:2006,
section 4.4.2 (EMC).
Ì
Please pay attention to any interference fields from devices such as frequency converters or induction
heating systems. Observe the EMC instructions in the manuals from the respective manufacturer.
Important!
If the device does not appear to function when operating voltage is applied (e.g. green STATE LED
does not flash), the locking module must be returned unopened to the manufacturer.
11.1. Notes about
Important!
Ì
This device is intended to be used and applied with a Class 2 power source.
Alternative solutions must comply with the following requirements:
This device shall be used with a suitable isolating source in conjunction with a fuse in accordance
with UL248. This fuse should be designed for max. 3.3 A and should be integrated into the 30 V DC
voltage section.
Ì
For use and application as per the requirements of UL
1)
a connecting cable listed under the UL
category code CYJV/7, min. 24 AWG, min. 80 °C, must be used.
1) Note on the scope of the UL approval: the devices have been tested as per the requirements of UL508 and CSA/ C22.2 no. 14 (protection against electric shock and fire).