ETH-messtechnik gmbh
D-74415 Gschwend P.O. 16
Nr.: 162e
Operating Instructions GMV2-K
revised: 09.05.2019
Rev.: 0
Subject to change without prior notice
22
9.4 Parameter set display
Menu paths:
1.) Menu-> Parameter-> ParSet-> Display
2.) Menu-> Output-> Display-> Param
The function for displaying individual parameters in a set can be called up in two different ways.
A parameter set is output to the LCD display in a maximum of six pages:
You can page through a parameter set with “Page+” or “Page-”. As soon as the last page is displayed, the first page is
displayed again. Empty pages are automatically skipped. A word in [...] means that this word is only displayed when the
function is enabled.
1. Setting 1
:
2. [Setting 2
:]
[Displays the settings for filter time, speed, power and continuous output]
3. [Setting 3
:]
[Parameter set text, settings for data record ID and operator number]
4. Torque
:
All torque values are displayed here
5. [Angle:]
[Displays all angle limits values (optional: only available with Version AW)]
6. Times
:
Displays all times (only available for peak measurements)
The display begins with the first page of the current set. Another parameter set can be displayed now with "Param +" or
"Param -". The page selection is not affected. Parameters from different sets can thus be compared with each other.
9.5 Printout of the Parameter Set
Menu path:
Menu-> Output-> RS232-> Param
All parameter sets are printed out in succession by pressing the "all" key. You may also select an individual set with
"Param +" and "Param -". Hit the OK key to print out this set.
Parameter sets cannot be printed out on the DP-1 HS (optional)!
Sample printout of parameter sets:
Output Param
-------------------------
Component 0815-01
PAR: 3
Transd: 200 Nm
Input
Type: 5V Cur2Ran
large_range
Zeroadjust: automatic
Overload: 25 %
Op. mode: Peak
Rot Dir: CW
Torque
- Lim max: 150.0 Nm
- Lim min: 100.0 Nm
- Shutoff: 120.0 Nm
Angle: none
Timing
- Suppr.: - -
- After: undef.
ErasrTm: - -
Store setting: none
Data record length: undef.
-------------------------
Wheel rim-III
PAR: 5
Input: 3.320V active
Zeroadjust: automatic
Overload: 50 %
Transducer: 1000 Nm
Mode: Pulse screwdr
Rot Dir: CCW
Co. fact: 86 %
Torque
- Lim max: -800 Nm
- Lim min: -300 Nm
- Shutoff: - -
- Trigger: -200 Nm
Angle: none
Timing
- Suppr.: - -
- After: 1000 ms
- ErasrTm: 1 s
Op. no.: yes
DR ID: yes
Store setting: CanTime
Data record length: 6
Input:
Socket designation, Input type
Transducer:
Transducer full scale value, [measuring range]
Input signal, overload range [,automatic zeroing]
Mode:
[Direction,] measuring mode [,correction factor]
Memory
setting:
Memory setting
DatRec length:
Data record length
Содержание GMV2-K