 Setting the Main Door Open Time (Default: 5 Seconds)

a. Enter  

2    #

b. Enter the desired Door Open Time (1-99 seconds), followed by  

#

Example:  

2    #    1    5    #

  (15 sec. Door Open Time)

c. Return to Setp 3 or enter 

 *  *

  to exit programming.

Keypad Status After Step Completion
Step

Beep

Red LED

Green LED

a

Double Slow Flash Slow Flash

b

Triple

Slow Flash Solid

!

 Setting Latching Option (Default: Off)

a. Enter  

3    #

b. Select the desired latching option:

Off-  

0    #

Manual-  

9    9    #

Timed- Enter the desired time interval in hours (1-98), followed

by  

#

.

Example:  

3   #    8   #

  (Sets timed latching for 8 hrs)

c. Return to Step 3 or enter  

*  *

  to exit programming.

Keypad Status After Step Completion
Step

Beep

Red LED

Green LED

a

Double Slow Flash Slow Flash

b

Triple

Slow Flash Solid

!

   Configuring Output A (Default: Aux #1)

a. Enter  

4    #

b. Select one of the following:

!

 CCTV / External Light

1) Enter  

1    #

Содержание K1 ERM Series

Страница 1: ...Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com INSTALLATION INSTRUCTION MANUAL K1 ERM...

Страница 2: ...n this documentation at any time Document Information IOMK1 ERM Installation Operations Manual for the K1 34 ERM3 3x4 Keypad or K1 26 ERM3 2x6 Keypad with Encoded Relay Module ERM November 2005 This d...

Страница 3: ...11 Encoded Relay Module LED Status Indicators 11 Operation Notes 11 Using the K1 ERM with a PC 13 Connecting the K1 ERM to a PC 13 Installing the CD ROM 13 Using Keypad Programmer Software 14 Using K...

Страница 4: ...Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com iii...

Страница 5: ...coded Relay Module ERM The 500 user code system consists of either a 3x4 or 2x6 Keypad and an Encoded Relay Module ERM Keypad with ERM Part Numbers 3x4 Keypad with ERM K1 34B ERM3 Brass Finished Bezel...

Страница 6: ...umidity 3x4 Keypad Dimensions 5 1 8 H x 3 3 8 W x 7 16 D 13 x 8 6 x 1 1 cm 2x6 Keypad Dimensions 7 1 8 H x 1 3 4 W x 3 4 D 13 x 8 6 x 1 1 cm 3x4 Keypad Weight 16 oz 454 gm 2x6 Keypad Weight 4 4 oz 125...

Страница 7: ...ail Safe or a Fail Secure Non Fail Safe electronic locking device or other equipment It may also be configured as a dry contact relay output to control a gate operator or garage door opener The main o...

Страница 8: ...owing 1 CCTV or Light Controller First key press triggers a Timed Output 1 to 99 seconds 2 Auxiliary Output Manual Control or Timed Output 1 to 99 seconds 3 Third Door Users can be assigned to open a...

Страница 9: ...he door is opened without a code or if the door is left open longer than the Door Ajar Time setting RED BLACK GREEN VIOLET GRAY ORANGE and SHIELD These wires all connect to the ERM module CONFIGURATIO...

Страница 10: ...n the CLOCK terminal on the ERM circuit is connected to ground through time clock or other switch contacts all codes work normally When the CLOCK terminal is not grounded only those codes with 24 hour...

Страница 11: ...uld hear 4 beeps and the RED LED will flash and the GREEN LED will be solid 4 Now that the Keypad is in configuration mode enter 98 followed by You should hear 3 beeps indicating successful configurat...

Страница 12: ...ammed User Codes are erased and factory default settings are restored Keypad Reset In certain cases you may want to erase all user codes and restore system defaults To perform this procedure 1 Remove...

Страница 13: ...g error beep re enter 98 followed by To change the audible beep or illumination proceed as follows Otherwise go to step 6 a To change the audible beep enter the code as follows Code Audible Beep 201 N...

Страница 14: ...s unlocked latched A solid red LED indicates that the door is locked Depending on how the System Options are configured User Commands are used to operate Manual Latching The User Commands are trailing...

Страница 15: ...and the Keypad and puts the Keypad into Programming Mode If no further programming is required press to exit If the ERM receives more than three 3 invalid EC s in a row the unit will go into LockUp M...

Страница 16: ...ally Upon the first attempt to send an ERM packet with a non matching EC the device will be put into the LockUp mode and from that point until a new EC is pro grammed the unit will essentially be shut...

Страница 17: ...a PC Connecting the K1 ERM to a PC Connect the ERM to a PC using a serial cable not included through the Serial COM Port The K1 ERM is set for 9600 baud Installing the CD ROM Install the KeypadUtils12...

Страница 18: ...e user options authorizations double click the code line When finished save the code chart file in either protected or unprotected format and upload to the K1 ERM If program ming has been done at the...

Страница 19: ...ill record all actions of the K1 ERM You can also print up to the last 500 transactions The date and times are taken from the computer not the K1 ERM Set up If BIND is blank the log will only list the...

Страница 20: ...d Status After Step Completion Step Beep Red LED Green LED a Double Fast Flash Slow Flash b Triple Fast Flash Solid Note If you forget the Master Code locate and press the PROGRAM button on the ERM bo...

Страница 21: ...n LED a Double Slow Flash Slow Flash b Triple Slow Flash Solid Setting Latching Option Default Off a Enter 3 b Select the desired latching option Off 0 Manual 9 9 Timed Enter the desired time interval...

Страница 22: ...mple 4 2 0 Sets Auxiliary Device with Manual Operation Second Door 1 Enter 3 2 Enter the desired Door Open Time 1 99 seconds followed by 3 Select the desired latching method Off 0 Manual 9 9 Timed Ent...

Страница 23: ...1 Enter 2 2 Enter the momentary output time 1 99 seconds followed by or Enter 0 to set the auxiliary device for Manual Operation ON OFF followed by Example 5 2 0 Sets Auxiliary Device with Manual Ope...

Страница 24: ...the master code to unlock the door d Return to Step 3 or enter to exit programming Time Clock Input Default Prevent a Enter 7 b Enter 0 to prevent lockout c Enter 1 to lockout all users that do not h...

Страница 25: ...ens programming and causes 3 Proceed to one of the following seven programming options Adding a New User a Enter 1 b Enter the User ID 1 to 499 followed by c Enter the User Code PIN 3 8 digits followe...

Страница 26: ...D a Double Slow Flash Slow Flash b Double Slow Flash Fast Flash c Double Slow Flash Fast Flash d Double Slow Flash Fast Flash e Double Slow Flash Fast Flash f Triple Slow Flash Slow Flash Notes on Add...

Страница 27: ...horization 2 Program or Delete Users Authorization 3 Output AAuthorization see notes 4 2nd Door see notes 5 Output B Authorization see notes 6 3rd Door see notes 7 24 hour Access see notes e Enter to...

Страница 28: ...modify an additional User return to Step b g If no more Users are to be modified enter and return to Step 3 or if you have completed all User Programming enter a second time to complete programming s...

Страница 29: ...y User a Enter 6 b Enter the User Code PIN 3 8 digits followed by c Enter the desired Temporary access Time 1 99 hours followed by d For 24 hour Access enter 0 for No or 1 for Yes followed by e Enter...

Страница 30: ...D s Codes and Authorizations Once an authorized user completes steps 1 2 to open the memory any combination of adding modifying or deleting Users can be performed without having to re enter Steps 1 2...

Страница 31: ...nnect the ERM Module to the serial port 3 To Log In the Keypad must not be in the following modes Setup Programming or Door Input Active 4 Once logged in the Keypad will not function until the user ex...

Страница 32: ...r de USER Insert the Temp Code in tmp PIN EXPTIME OPTIONS Modify the Temp Code mo tmp PIN EXPTIME OPTIONS Delete the Temp Code de tmp List a User le USER or tmp for Temp Code List all Users la List al...

Страница 33: ...29 Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com K1 ERM Series Diagrams ERM Circuit Board 2...

Страница 34: ...Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com 30 Typical Hook up Fail Safe or Fail Secure and CCTV Diagram...

Страница 35: ...31 Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com Notes...

Страница 36: ...any replacement furnished under this warranty beyond the unexpired portion of original part warranty given on the original part or system which has been replaced Essex Electronics Incorporated s liabi...

Страница 37: ...lay Module ERM The original of any system replaced under this warranty shall become our property and as such will at our request be returned to our factory with transportation charges replaced by the...

Страница 38: ...BOVE UNDER NO CIRCUMSTANCES WILL ESSEX ELECTRONICS INCORPORATED BE LIABLE TO BUYER UNDER OR IN CONNECTION WITH ANY MANUFACTURE OR SALE OF THE K1 ERM ENCODED KEYLESS ENTRY ACCESS CONTROL SYSTEM OR ENCO...

Страница 39: ...ate of California in and for Santa Barbara County California Repair Policy Should it be necessary for a component or a system to be returned for repair it must be accompanied with an RA Return Authori...

Страница 40: ...Essex Electronics Inc 805 684 7601 800 KEY LESS fax 805 684 0232 keyless com...

Отзывы: