background image

11

1 Electrical manual mode 

To allow testing at start-up or in the event of malfunctions such as sensor defects, the 
controller sequence can be overridden using electrical manual mode , the pump swit-
ched on and the mixing valve moved to the desired position.
To do this, select the “Mode” menu from the main menu by using the buttons marked 
with an arrow and then pressing the select button. Change the mode to manual.
The red LED will flash to indicate that manual mode is active and the mixing valve can 
be moved to the desired position using the OPEN and CLOSE buttons. The pump is on 
while this is happening. To quit manual mode, press the ESC button and the control will 
return to the previous mode.

2 Mechanical manual mode 
Please note:

 Mechanical manual mode must only be used if the 90C controller is in 

electrical manual mode or disconnected from the power supply.
In exceptional circumstances, e.g. if the motor or gears are damaged, the mixing valve 
can be moved into the desired position manually. To do this, put the 90C controller 
into electrical manual mode as described above and then press in the grey mechanical 
release button. While this is being done, the mixing valve can be adjusted manually 
using a size 20 spanner. Once the mixing valve has been adjusted, the spanner must 
be removed to prevent the unit from being damaged. To return to automatic mode, the 
mixing valve needs to be turned by the spanner and without the release button being 
pressed until the release button engages again. 

The top line of the display shows either the menu that can be selected, the setting to be 
made, the operating state, the relevant temperature or general information.
The bottom line of the display explains the current function of the three buttons in rela-
tion to the information on the top line of the display. Key to button functions:

< or >

 

Scroll from one menu option to the next and 

 

back without any changes being made.

Select

 

Opens the displayed menu.

esc

 

Exits the current settings menu without saving  

 

any changes that have been made.

Change

 

Enters the particular menu option to make  

 

adjustments.

–  or  +

 

Increases/decreases the displayed setting.

OK

 

Confirms the current display/setting.

Yes

 

Confirms the current display.

No

 

Rejects the current display.

Please note:

 If a button is not pressed within 5 minutes, the unit will automatically 

return to normal operation with status display: 
Current temperature readings from the outside and flow pipe sensors, the target flow 
temperature and the operating state of pump and mixing valve.
The date and time will appear on the display briefly from time to time together with the 
current control mode. If a button is not pressed within 6 minutes, the display illumina-
tion will be switched off.

Exception:

 If the controller is in manual or setpoint mode.

“01 Temperatures” menu 

The current temperatures are displayed in this menu. First a summary of outside tem-
perature, (target flow temperature) and actual flow temperature appears.
Each of these values and the correction value of the optional room sensor can be 
displayed individually in plain text by pressing a button.

“02 Operating Periods” menu 

This menu is used to set the day operating periods for the heating circuit. They can 
either be set as a daily program (every day the same) or weekly program (each day 
separately).
Up to three day operating periods can be selected for the heating circuit each day. It is 
possible to specify whether or not each day operating period is to have an additional 
comfort boost.
Outside the day operating periods the controller operates in reduced night mode.
The day operating periods can be set between 00.00 and 24.00 daily. If the second or 
third day operating period is not needed, the start of those periods should be set to 
24.00 to prevent further day operation from taking place.
Day correction, comfort boost and night reduction are explained in more detail in sec-
tion “03 Settings” menu.

“03 Settings” menu

 

This menu is used to enter settings for the controller function and therefore the desired 
temperature level. Factory settings are shown in bold text.

S/W day  

18°C

  

(setting range 10...30°C) 

Select the outside temperature at which the controller should switch between summer 
and winter in day mode. 
Summer mode: When the selected temperature is exceeded, the mixing valve closes 
completely and the heating-circuit pump is turned off.  
Winter mode: If the temperature drops below the set value, controller is resumed.

S/W night  

12°C 

 

(setting range 10...30°C) 

The same as for S/W day, but this setting is for the night operating period.

FT>HC off  

15°C 

(setting range 7...30°C) 

If the target Flow Temperature is below the Heating Curve value set here, the mixing 
valve closes and the circulation pump in the heating circuit is turned off. 

Emergency/Manual mode (for use by qualified persons only)

Menu navigation – setting and checking parameters

Содержание 90C Series

Страница 1: ...ESBE Regulator Serie 90C...

Страница 2: ...2 CLICK 1 5 5 5 5 5 5 3G 3MG 3F 5 5 2 3...

Страница 3: ...3 Svenska 4 8 English 9 13 Deutsch 14 18 Fran ais 19 23...

Страница 4: ...k nna igen p den r da st ll skivan med pilmarkeringar Eftersom serie 90C regulator kommer i ett utf rande d r kabeldragningen redan r gjord har man minimerat monteringsinsatsen och risken f r installa...

Страница 5: ...e N Brun Fas L 5 Rumsgivare S3 Om man vill komplettera med nnu en givare t ex i vardagsrummet ska anslutningen g ras p f ljande s tt Skala av en kabel p 2x0 75mm2 med max 40mm och f r in den i den led...

Страница 6: ...rdesdrift stannar regulatorn i denna meny och statusvisningen kopplas inte in Meny 01 Temperaturer I den h r menyn visas de aktuella temperaturv rdena F rst visas en versikt med utetemperatur b r fra...

Страница 7: ...ch p s s tt spar man energi Exempel En dagskorrigering p 5K och en natts nkning p 2K ger en b r framled ningstemperatur reducerad med 7 C vid nattdrift Meny 04 Drifts tt I den h r menyn kan regulatorn...

Страница 8: ...ngstemperaturen till minst 20 C f r att skydda v rmekretsen mot frostskador Om utetemperaturen verstiger 2 C tas normaldriften upp igen Fabriksinst llningen r frostskydd P I drifts tten manuell b rv r...

Страница 9: ...ing valve and Direction of rotation are indicated simply and clearly on the red adjusting disc by means of an arrow Because the 90C controller is prewired installation work is kept to a minimum and er...

Страница 10: ...ug the preconnected cable labelled power supply into a 230 V 50 Hz socket outlet with earthing contact Wiring Green yellow Earth PE Blue Neutral N Brown Phase L 5 Room sensor option S3 If a room senso...

Страница 11: ...omatically return to normal operation with status display Current temperature readings from the outside and ow pipe sensors the target ow temperature and the operating state of pump and mixing valve T...

Страница 12: ...ons frequently occur if the characteristic has not been optimised In hot weather living space too cold In cold weather living space too hot If this happens reduce the characteristic heating curve in s...

Страница 13: ...of rotation will have to be changed To do this use a small screwdriver to lever the transparent disc off the front carefully change the sticker and put the transparent disc back together with its rubb...

Страница 14: ...sind an der roten Stellscheibe mit Pfeilmarkierung einfach und bersichtlich erkennbar Aufgrund der vorverkabelten Ausf hrung des Serie 90C Control ist der Montage aufwand minimiert und Installationsfe...

Страница 15: ...ist das Kabel vom Fachmann zu entfernen 4 Netzanschluss Achtung 230 VAC Das bereits im Auslieferzustand angeschlossenen Kabel mit der Bezeichnung power supply ist an einer Schutzkontaktsteckdose mit...

Страница 16: ...st tigt die aktuelle Anzeige den Einstellwert ja Best tigt die aktuelle Displayanzeige nein Die aktuelle Displayanzeige wird abgelehnt Hinweis Wird innerhalb von 5 Minuten keine Taste bet tigt schalte...

Страница 17: ...lheit von 1 2 als Einstellwert Tageskorr 5K Einstellbereich 0 50K Durch die Tageskorrektur wird eine Parallelverschiebung der Heizungskennlinie w hrend der Tagbetriebszeiten vorgenommen da es vorkomme...

Страница 18: ...htung Festlegen von AUF und ZU In Werkseinstellung f hrt der Mischer bei Rechtsdrehung ZU und bei Linksdrehung AUF Diese Funktion kann hier je nach Einbau des Mischventils invertiert werden In diesem...

Страница 19: ...service normal La position de la vanne de m lange et son sens de rotation sont clairement visibles gr ce la fen tre circulaire laissant appara tre les zones rouge ou bleue Le moteur r gulateur 90C ta...

Страница 20: ...e par exemple dans la salle de s jour proc der comme suit c ble non fourni Utiliser un c ble isol 2x0 75mm2 d nuder les deux conducteurs sur une longueur de 40 mm maxi passer le c ble par le presse to...

Страница 21: ...circuit Temp rature actuelle d part circuit Etat de la pompe et de la vanne de m lange L clairage de l cran s teint apr s 6 minutes Exception si le r gulateur est en mode manuel ou temp rature consta...

Страница 22: ...ion Lorsque que la courbe n est pas optimis e les effets suivants peuvent r guli rement tre ressentis Par temps chaud pi ces trop froide Par temps froid pi ces trop chaude Si tel est le cas r duire la...

Страница 23: ...ta tion peut tre invers Dans ce cas l autocollant rouge et bleu sur la fa ade de l appareil indiquant le sens de rotation devra tre remplac en ouvrant l appareil Hors gel Si la temp rature ext rieure...

Страница 24: ...Art nr 25725 Ritn nr 3726 Utg A Rev 0506...

Отзывы: