4
[ 10 ]
Х10 - fitting with additional equipment:
–
SZK IP535 - protective visor
–
other equipment (designation by agreement with the customer).
Omission or alteration of the data sequence [5-10] in designation of the product is allowed as
well as insertion of other punctuation marks between the data that does not lead to a different
interpretation of the product version.
Examples of reference designation of the IP535-07ea-RS call point:
‘IP535-07ea-RS-A, KVO14, KVO14, SZK IP535’
‘IP535-07ea-RS-START LAUNCH OF FIRE SUPPRESSION (ZH)/ KVM15, ZG’.
Examples of the IP535-07ea-RS call point description when ordering:
‘Explosion-proof addressable manual call point IP535-07ea-RS-A, KVO14, KVO14, SZK
IP535 - 2 units’
‘Explosion-proof remote start device IP535-07ea-RS-START/LAUNCH OF FIRE
SUPPRESSION (ZH)/ KVM15, ZG’.
Examples of the IP535-07ea-RS call point description when drafting documents:
‘Explosion-proof addressable fire manual call point IP535-07ea-RS-A, KVO14, KVO14, SZK
IP535, TU 4371-006-43082497-04’
‘Explosion-proof addressable remote start device IP535-07ea-RS-START/LAUNCH OF FIRE
SUPPRESSION (ZH)/ KVM15, ZG, TU 4371-006-43082497-04’.
2.
TECHNICAL DATA
2.1.
Pursuant to GOST R 53325-2012, the call point IP535-07ea-RS is an A or B class fire
manual call point (depending on the version), the device IP535-07ea-RS-START is a class B fire
manual call point.
2.2.
Power supply and data exchange of the call point are provided via the four-wire
communication line: 2 wires - RS-485 line, Modbus RTU protocol, 2 wires - electrical power
supply.
The call points must be connected to communication line in parallel, with strict observation of
polarity.
2.3.
Maximum number of addressable devices to be connected: 32.
2.4.
The call point is energized from a direct current source with a rated voltage of 24 V
±10%. The call point remains operational within the range of supply voltages from 8 V to 28 V.
2.5.
Maximum current consumption value: 20 mA.
2.6.
Maximum warm-up time of the call point after powering up is 1 sec.
2.7.
In accordance with clause 4.2.1.10 of GOST R 53325-2012 resetting of the call point
from ‘Activated’ mode to standby mode is possible only when the driving element is installed after
receiving a ‘Device reboot’ or ‘Registered events reset’ command from the control device (in case
the ‘Activation registration’ function is activated, register 50; see Annex B) or when the call point
is powered down.
In case the ‘Activation registration’ function is deactivated, the minimum time of fixation in
‘Activated’ mode is 10 sec.
In order to comply with GOST R 53325-2012 and when operating the call point in the territory
of Russia, the ‘Activation registration’ function must be activated.
2.8.
Optron relays status in standby mode by default:
–
Р1 (notification ‘Activated’) normally-open (NO)
–
R2 (notification ‘Fault’) normally-closed (NC).
The relays are programmable, for configuration of the initial relay status in register 50, see
Annex B.
2.9.
Optron keys parameters:
–
maximum switching current 100 mA
Содержание IP535-07ea-RS
Страница 20: ...20 b Appearance of the call point IP535 07ea B...