Eridan IP535-07ea-RS Скачать руководство пользователя страница 9

485 

●  Constant red glow 

(independently of the green 
indicator) 

Constant glow 

‘Activated’ operation 
mode 

● 

●  Green and red constant glow  Constant glow 

A failure has been 
registered 

5.

 

PROVISIONS FOR EXPLOSION PROOFNESS 

5.1.

 

In terms of explosion protection, the explosion-proof call point IP535-07ea-RS meets the 

requirements of TR CU 012/2011, GOST 31610.0-2014 (IEC 60079-0:2011), GOST IEC 60079-1-
2013, GOST IEC 60079-31-2013. 

5.2.

 

The assembled call point with installed cable glands is an explosion-proof enclosure that 

meets  the  requirements  of  GOST  31610.0-2014  (IEC  60079-0:2011)  for  electrical  equipment  of 
groups II and III with high level of mechanical damage hazard. The call point casing has protection 
IP66/IP67 as per GOST 14254-2015 (IEC 60529:2013). 

5.3.

 

Explosion-resistance  of  the  call  point  is  achieved  by  means  of  application  of  explosion 

resistant threaded and sealed connections as per GOST IEC 60079-1-2013. 

Strength of each casing is checked during manufacturing via hydraulic tests by 1.5x explosion 

pressure during the time necessary for inspection but not less than 10 seconds. 

5.4.

 

Dust  ignition  protection  is  provided  by  means  of  application  of  ‘protection  from  dust 

ignition by means of ‘t’ enclosures’. The parameters of connections of the casing elements comply 
with the requirements of GOST IEC 60079-31-2013. 

5.5.

 

Cable glands ensure strong and stable sealing of cables. Sealing elements and plugs meet 

the requirements for explosion proofness as per GOST IEC 60079-1-2013. 

5.6.

 

The explosion-proof manual fire  call point must be used with cable glands and plugs of 

the  manufacturer  or  other  certified  cable  glands  and  plugs  that  provide  explosion  protection  type 
‘explosion-proof  enclosure’  and  explosion  protection  level  1.  The  protection  degree  (IP)  and  the 
operating  temperature  range  of  cable  glands  should  correspond  to  the  operating  conditions  of  the 
call point. 

5.7.

 

Composition of the materials used for call point production provides its frictional intrinsic 

safety and meets the requirements of GOST 31610.0-2014 (IEC 60079-0:2011). 

5.8.

 

The  maximum  heating  temperature  of  outer  surface  of  the  call  point  enclosure  under 

normal  and  emergency  conditions  does  not  exceed  the  values  admissible  for  electrical  systems  of 
the temperature classes Т6 as per GOST 31610.0-2014 (IEC 60079-0:2011). 

5.9.

 

On  the  call  point's  body  there  is  a  nameplate  indicating  explosion  proofness  markings, 

and on the cover, there is a warning ‘Unplug before opening’. 

5.10.

 

Explosion-proof surfaces of the cover and the body are covered with anti-corrosion heat 

resistant grease as per GOST 9433-80. 

5.11.

 

The spring washer prevents the grounding clamp from loosening. 

5.12.

 

Sealed  lashing  on  the  driving  element  prevents  the  cover  of  the  explosion-proof  casing 

from self-unscrewing (to be installed by the customer). 

6.

 

PROVISIONS FOR EXPLOSION PROOFNESS DURING INSTALLATION 

6.1.

 

Conditions  of  operation  and  installation  of  the  call  point  must  meet  the  provisions  set 

forth  in  TR  CU  012/2011,  GOST  IEC  60079-14-2013,  Chapter  7.3  of  the  EIC  (version  6), 
Regulations  for  operation  of  consumer  electrical  installations,  Chapter  3.4,  safety  regulations  and 
any other regulations as may be effective in the industry where the call point is applied. 

6.2.

 

The  call  points  must  be  used  in  accordance  with  the  established  explosion  proofness 

marking. Possible explosive areas of application, categories and groups of explosive gas, vapor and 
air mixes are in accordance with the requirements of GOST IEC 60079-10-1-2013 and Chapter 7.3 

Содержание IP535-07ea-RS

Страница 1: ...nel e mail market eridan zao ru http www eridan ru 2 26 30 50 121 Explosion Proof Addressable Manual Fire CALL POINT IP535 07ea RS Modbus RTU protocol Operation Manual 4371 006 43082497 04 04 2021 EXP...

Страница 2: ...degree IP and the operating temperature range of cable glands should correspond to the operating conditions of the call point The call point can be installed in class 1 and 2 indoor explosive areas an...

Страница 3: ...vice UDP 4 X4 designation of the version variant for the IP535 07ea RS call point call point class as per GOST R 53325 2012 A class A one step activation B class B activation by performing several act...

Страница 4: ...l point are provided via the four wire communication line 2 wires RS 485 line Modbus RTU protocol 2 wires electrical power supply The call points must be connected to communication line in parallel wi...

Страница 5: ...r normal climatic conditions withstands a sinusoidal alternating voltage of 0 55 kV 50 Hz during one minute 2 17 Electrical resistance of insulation between the connected output conductors and the cal...

Страница 6: ...otection degree IP and the operating temperature range of cable glands should correspond to the operating conditions of the call point By agreement with the customer call points can be equipped with d...

Страница 7: ...al power supply The call points must be connected to communication line in parallel with strict observation of polarity Connection diagrams of the call point are shown in Annex B In order to configure...

Страница 8: ...s will cause the instrument to receive the Activated signal from the call point device it will display the corresponding message and will send back to the call point an acknowledgement of successful s...

Страница 9: ...explosion protection type explosion proof enclosure and explosion protection level 1 The protection degree IP and the operating temperature range of cable glands should correspond to the operating co...

Страница 10: ...cover and the body 6 12 The call point must be sealed after installation 7 SAFETY PROVISIONS 7 1 Compliance with the safety rules is mandatory for safe operation and use of the call points 7 2 Any wor...

Страница 11: ...n of the call point at the facility must follow the predesigned plan taking into consideration all the requirements hereof 8 5 Prior to installation of the call point at the site remove plugs from the...

Страница 12: ...ible 8 21 Check the completed installation by drawing attention to the correctness of the connections the presence of all fastening and locking elements and their correct installation 8 22 Close the c...

Страница 13: ...r and its address Customs Union conformity mark name or logo of certification authority and number of the certificate of compliance 9 3 The sequence of marking records is determined by the manufacture...

Страница 14: ...1 0 h 10 5 It is strictly prohibited to operate the call point with damaged explosion proof parts and any other defects 10 6 Opening of the call point cover and inspection are only allowed after all...

Страница 15: ...he fire device 11 3 In case of other more complicated failures their elimination can be carried out only at the manufacturer s factory Eridan JSC 11 4 In case of the call point s failure there are no...

Страница 16: ...al rules of cargo transportation 12 3 During transportation the requirements of the manipulation signs on the transportation packages must be strictly complied with During cargo handling and transport...

Страница 17: ...omer 14 CLAIM INFORMATION 14 1 Claims regarding quality of the call point are accepted upon submission of the call point this technical certificate and the report on hidden defects 14 2 The manufactur...

Страница 18: ...ed by the Certification Authority OS POZHTEST of FGBU VNIIPO of Emercom of Russia Certificate of compliance with the Technical Regulations of the Customs Union TR CU 020 2011 EAEU No RU RU 40 00693 20...

Страница 19: ...holes for sealing with the driving element the arrows on the call point nameplate must face vertically down as per the figure 7 lens 15 disk 23 24 washer 21 bolt 27 magnet 28 sealing ring 29 LED 30 b...

Страница 20: ...20 b Appearance of the call point IP535 07ea B...

Страница 21: ...3 removable element 4 body 6 cover the arrows on the device nameplate must face vertically down as per the figure 7 lens 8 protective element 15 disk 23 24 washer 21 bolt 27 magnet 28 sealing ring 29...

Страница 22: ...ble in cable gland KVBU 1 sheath wall maximum diameter for cable entry Dc 12 mm 2 cable insulation 3 sealing ring along the cable wrapping L 20 mm in uncompressed condition 4 washer 5 lock nut 6 union...

Страница 23: ...exceeding 2 5 mm is not allowed 2 insert the wire free from insulation into the inlet of the terminal 3 clamp the wire by releasing the terminal wrench or the screwdriver after that self disconnectin...

Страница 24: ...2 Terminal board of the call point IP535 07ea RS Table 5 The terminals designation for the call point IP535 07ea RS No of socket No of contact Designation of contact Description 1 1 6 Usup Feed throug...

Страница 25: ...of the contacts of the relay R2 Failure Terminal RTERM and additional RADD resistors are selected in accordance with FACP operation manual Install the jumper in terminals 3 7 of socket 2 of the call p...

Страница 26: ...f the call point Figure 5 Diagram of connection of the call point to fire alarm loop activated by closing The off position of the relay R1 Activated is configured as normally closed NC The call point...

Страница 27: ...ask and OR mask 0 17 reading and recording of various storage registers 0 2B 0 0E reading of device identifier processing of broadcast packets with a slave device address equal to 0 There is no respon...

Страница 28: ...ersion 0 65535 3 0x0008 8 0 03 UINT Serial number Lo 0 65535 0x0009 9 0 03 UINT Serial number Hi 0 65535 0x000A 10 0 03 UINT Device general status 1 6 1 booting 2 test 3 normal 4 acknowledgement reque...

Страница 29: ...t is activated 0 Installed 9 15 Reserve 14 Table 8 Configuration register register 50 0 0032 Bit No Designation Note 0 1 Activated signal is registered before reveiving a reset command status registra...

Отзывы: