ENVIRO-TEC
72
FORM ET115.24-NOM4 (819)
SECTION 6 - DIMENSIONAL DATA
TABLE 19 -
DISCHARGE REGISTER PERFORMANCE DATA, VH STANDARD FCU 79" CABINET, SINGLE
AND DOUBLE SUPPLY
SINGLE SUPPLY
UNIT
SIZE
CFM
(SEE NOTE 5)
REGISTER DATA
W (IN.)
H (IN.)
Pv
(in W.G.)
Pt
(in W.G.)
Ps
(IN W.G.)
NC
THROW
(FT)
DROP
(FT)
03
375
16
8
0.013
0.0370
0.0240
<20
13-32
10
04
450
16
8
0.018
0.0524
0.0344
23
20-39
10.5
06
616
18
8
0.026
0.0765
0.0505
32
20-39
10.5
08
860
18
8
0.054
0.1624
0.1084
39
32-54
17
DOUBLE SUPPLY
UNIT
SIZE
CFM
(SEE NOTE 5)
REGISTER DATA
W (IN.)
H (IN.)
Pv
(in W.G.)
Pt
(in W.G.)
Ps
(IN W.G.)
NC
THROW
(FT)
DROP
(FT)
03
375
16
8
0.003
0.0072
0.0042
<20
8-25
9
04
450
16
8
0.005
0.0160
0.0110
<20
9-25
10
06
616
18
8
0.007
0.0180
0.0110
<20
13-30
10
08
860
18
8
0.015
0.0380
0.0230
21
18-39
11
10
966
22
8
0.015
0.0380
0.0230
<20
17-42
12.5
12
1350
22
8
0.019
0.0560
0.0370
21
21-45
14
NOTES:
1. NC data is at 0
°
deflection. For 22.5
°
deflection, add 1 NC. For 45
°
deflection, add 7 NC.
2. Throws are for velocities of 50 and 150 FPM at 0° deflection.
3. For 22. 5° and 45° deflection, multiply by 0.67.
4. Drops are at 0° deflection. For 22.5° deflection, multiply by 0.85. For 45° deflection, multiply by 0.66.
5. Register Data is based on zero static and CRM show at high speed motor operation.
6. Data above does not reflect optional opposed blade damper information.
Содержание VHA
Страница 10: ...ENVIRO TEC 10 FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 22: ...ENVIRO TEC 22 FORM ET115 24 NOM4 819 SECTION 1 RECEIPT INSTALLATION THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 41: ...ENVIRO TEC 41 SECTION 2 START UP FORM ET115 24 NOM4 819 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 54: ...ENVIRO TEC 54 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data 74 80083 ...
Страница 78: ...ENVIRO TEC 78 FORM ET115 24 NOM4 819 SECTION 6 Dimensional Data NOTES ...