Installation

H

oRizontaL

 e

XHaust

 t

HRougH

 W

aLL

 i

nstaLLation

:

Vent installation: install vent at clearances specified by the vent manufacturer.

A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces, 

or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired, 

the installation must conform to CAN/CSA-B365 Installation Code for Solid-Fuel-Burning Appliances and 

Equipment  and  with  all  local  regulations,  including  those  referring  to  regional  and  national.  Only  use 

venting of L or PL type or corn certified venting if corn will be burned as a fuel with an inside diameter of 4 

inches (100 mm). All joints in the exhaust venting system must be fastened with at least three (3) screws.

NOTE:

• It is recommended that horizontal through wall installations have a “T” and 3 to 5 feet (91 to 152 cm) 

of vertical pipe in the system to help naturally draft the unit in the event of extreme weather or a power 

outage.  This may also be required if a proper burn cannot be maintained, after the stove has been 

tested and the airflow set. This is due to the back pressure in the exhaust caused by airflow around 

the structure.

• Follow vent manufacturer guidelines for installation, clearance to combustibles, and sealing of venting. 

High temp Sealant must be used when connecting vent pipe to the unit’s starter pipe. Improper seals 

at the vent joints may cause combustion by-products to leak into the room where installed - seal as 

required by vent manufacturer.

1. Locate  the  center  of  the  exhaust  pipe  on  the  wall,  refer  to  pellet  vent  manufacturer  installation 

instructions for correct hole size and clearance to combustibles.

2. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour 

barrier in accordance with local building codes.

3. Install a length of vent pipe into the wall thimble. Try not to have joints inside the thimble. The pipe 

should install easily into the thimble.

4. Connect  the  exhaust  vent  pipe  to  the  exhaust  pipe  on  the  stove.  Seal  the  connection  with  high 

temperature silicone.

5.  The  pipe  must  extend  at  least  12”  (30  cm)  away  from  the  building.  If  necessary,  bring  another 

length of pipe to the outside of the home to connect to the first section. Do not forget to place high 

temperature silicone around the pipe that passes through the thimble if required by vent manufacturer.

6.  Install vent termination or 3-5’ of vertical pipe and a 90 degree elbow and vent termination.

24

Содержание M55-FPIs640

Страница 1: ...LD RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH Contact your building or fire officials about restrictions and installation inspection requirements in your area W A R R A N T Y R E G I S T R...

Страница 2: ...o Locate Your Pellet Appliance 16 Removing Pellet Stove From Pallet 16 Installing the Inset Frame and Levelling 17 Clearances to Combustibles 18 Thermostat Installation 18 Vent Termination Requirement...

Страница 3: ...ove needing to be cleaned daily A low ash fuel may allow longer intervals between cleaning CLINKERING clinkers are silica sand or other impurities in the fuel that will form a hard mass during the bur...

Страница 4: ...15 2015 Under specific test conditions this heater has been shown to deliver heat at rates ranging from 9 200 45 500 Btu hr Emissions Rating Label Serial No DATE OF MANUFACTURE J F M A M J J A S O N...

Страница 5: ...again until you are certain the chimney and its lining have not been damaged OPERATION The door and ash drawer must be kept closed when the unit is in operation to prevent fume spillage and for prope...

Страница 6: ...y suitable measures e g load distributing plate must be taken to achieve it DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING A...

Страница 7: ...pe Residential Pellet Heater 6mm dia Pellets wood corn wheat barley Voltage Current Max Power 110 120 V 4 2 Amps 504 Watts Frequency Hopper Capacity Consumption on Low 60 Hz up to 50 lb 22 7 Kg 1 5 lb...

Страница 8: ...feed settings When pressed all lights on Heat Level Indicator will come on except the one that is the set point Hold Trim Button down and press the UP or DOWN Heat Level Arrow to adjust setting 3 Lig...

Страница 9: ...t operate for the first five minutes after the ON button has been pressed After the ten minutes it will pulse at the same interval as the feed auger When the start up sequence is complete the unit wil...

Страница 10: ...water column 37 42 Pa This can be measured using a Magnahelic pressure gauge once the unit has been running on heat level 5 setting after one hour of burn time This adjustment is necessary for varyin...

Страница 11: ...o adjust this cover either up or down to control the maximum output of 55 000 BTU Lowering the cover position will decrease output and raising it will increase output CAUTION Increasing output too muc...

Страница 12: ...it 3 The agitator locks at the right rotate the top of the agitator towards the back of the firebox to unlock it slide it to the left and lift it out of the burn pot liner 4 Lift the burn pot liner o...

Страница 13: ...use the gasketing may come loose To repair this glue the gasketing on using high temperature fiberglass gasket glue available from your local dealer This is important to maintain an airtight assembly...

Страница 14: ...N CLEAN UP Once you are finished using the pellet appliance for the season unplug the stove for added electrical protection It is very important that the stove be cleaned and serviced as stated above...

Страница 15: ...2 Close up of Front Rail Quick Release Pin Thumb Screw 1 Remove Cast Ash Drawer Front 2 Slide open the Cast Top 3 Lift off Cast Sides 4 Clip Side Rails to unit 5 Attach Front Rail using the quick rele...

Страница 16: ...l units installed in Mobile and Air Tight Homes R2000 or where required by local codes 7 Do not obtain combustion air from an attic garage or any unventilated space Combustion air may be obtained from...

Страница 17: ...e length of the bolts masonry bricks may be placed under the frame 4 Once level position the Insert Frame in the fireplace cavity so that the Surround Panel is flush with the front of the fireplace 5...

Страница 18: ...matically O will drop down t will return to pre and it will restar To Turn Off Stov AUTO OFF mo Pour d marrer qualit de supe carburants App pot de br lure h Pour faire fonct MODE HIGH L tre ajust s L...

Страница 19: ...llowable exterior vent termination locations Table 2 Use in conjunction with Figure 6 for allowable exterior vent termination locations Letter Minimum Clearance Description A 24 in 61 cm Above grass t...

Страница 20: ...mes When connecting to an outside fresh air source do not use plastic or combustible pipe A 3 minimum 76 mm ID inside diameter steel aluminum or copper pipe or ducting should be used The inlet must ha...

Страница 21: ...Chimneys 6 It is necessary to permanently seal any opening between the masonry of Figure 9 Masonry fireplace installation the fireplace and the facing masonry When installing the insert into a masonry...

Страница 22: ...from the fireplace from entering the chimney which will affect proper drafting of appliance Figure 10 Masonry fireplace positive flue installation A qualified installer should evaluate the existing fi...

Страница 23: ...st be supported with sheet metal studs and have no combustible material in the air space All venting for Built In installation must use PL or L venting and be installed with vent manufacturer s recomm...

Страница 24: ...st caused by airflow around the structure Follow vent manufacturer guidelines for installation clearance to combustibles and sealing of venting High temp Sealant must be used when connecting vent pipe...

Страница 25: ...nation Installation Figure 12 Venting horizontally with rise NOTE This venting configuration is only for use with the Built In installation Wall framing Wall thimble Termination cap Vertical section o...

Страница 26: ...PL vent upward from the tee Make sure that you install support brackets to keep the vent straight and secure All joints in the exhaust venting system must be fastened with at least three 3 screws 3 I...

Страница 27: ...in the exhaust venting system must be fastened with at least three 3 screws 3 Install ceiling thimble and secure the flashing as you go through the roof 4 Ensure that the rain cap is approximately 24...

Страница 28: ...If the 3 light is flashing unit may be out of fuel Check the Door and Ash Pan door THEY MUST BE CLOSED TIGHT See section 8 The Fuel will not light Check the fuse on the circuit board If the unit still...

Страница 29: ...require vertical section to move termination into a low pressure zone To reset Circuit Board after a trouble code push the ON OFF button 5 Unit is on but auger motor does not turn at all Check the li...

Страница 30: ...of the Heat Level button make sure the thermostat is calling for heat Call your local dealer for service 10 The stove keeps going out If the stove goes out and leaves fresh unburned fuel in the burn p...

Страница 31: ...Grey Grey Orange Orange White Grey Grey White Blue Yellow Auger Motor White Yellow Vacuum Switch Connect Thermostat Here Brown Brown Blue Purple Yellow Red Thermostat Combustion Blower Black Black Whi...

Страница 32: ...uger Collar with Screw 50 968 14 Auger Motor 2rpm 50 2054 15 Exhaust Motor Capacitor including Strap 50 2053 16 Agitator Drive Shaft with Sprocket 50 1698 17 Motor Drive Sprocket 50 1700 18 Auger Moto...

Страница 33: ...of 2 50 2294 54 Bearings with Mounting Bolts Set of 4 50 2295 55 M55C FPI Milan Empress FPI 2 Amp Small Fuse 50 2302 56 M55C FPI Milan Empress FPI 4 Amp Small Fuse Ignitor 50 2303 57 Agitator Drive B...

Страница 34: ...2276 68 M55C FPI Cast Ash Door Chestnut 50 2282 68 M55C FPI Cast Ash Door DB 50 2299 69 M55C FPI Cast Surround Trim Only PD 50 2272 69 M55C FPI Cast Surround Trim Only Beach 50 2278 69 M55C FPI Cast...

Страница 35: ...Parts Diagram Components 6 48 1 2 3 4 8 23 14 10 11 15 9 29 21 7 42 24 12 54 25 17 16 18 40 5 22 45 41 49 47 52 53 13 19 20 37 35...

Страница 36: ...Parts Diagram Steel 69 70 38 28 57 26 27 63 5 62 61 36 51 59 66 67 68 64 65 30 37 39 44 36...

Страница 37: ...Notes 37...

Страница 38: ...Notes 38...

Страница 39: ...cluding serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caus...

Страница 40: ..._____________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy MAGNEHELIC AT INSTALL ___________________ INSTALLER S SIGNATURE ____________________________...

Отзывы: