2.  Vent  surfaces  can  become  hot  enough  to  cause  burns  if  touched  by  children.  Non-combustible  shielding  or 

guards may be required.

3.  Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be 

installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the 

possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a 

nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred 

venting method is to extend the vent through the roof vertically.

4.  Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the 

plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located 

in the vicinity of termination. The grade surface must not be lawn.

5.  If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior 

of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no 

guarantee against such incidents.

NOTE: Venting terminals shall not be recessed into walls or siding.

Installation

v

ent

 t

eRmination

 R

eQuiRements

:

IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER. 

Figure 6: Use in conjunction with Table 2 for allowable exterior vent termination 

locations. 

Table 2: Use in conjunction with Figure 6 for allowable exterior vent termination locations. 

Letter

Minimum Clearance

Description

A

24 in (61 cm)

Above grass, top of plants, wood, or any other combustible materials.

B

48 in  (122 cm) 

Beside/below any door or window that may be opened. (18” (46 cm) if outside 

fresh air installed.) 

C

12 in (30 cm)

Above any door or window that may be opened. (9” (23 cm) if outside fresh air 

installed.) 

D

24 in (61 cm)

To any adjacent building, fences and protruding parts of the structure.

E

24 in (61 cm)

Below any eave or roof overhang

F

12 in (30 cm)

To outside corner.

G

12 in (30 cm)

To inside corner, combustible wall (vertical and horizontal terminations).

H

3 ft (91 cm) within a height 

of 15 ft (4.5 m) above the 

meter/regulator assembly

To each side of center line extended above natural gas or propane meter/

regulator assembly or mechanical vent.

I

3 ft (91 cm)

From any forced air intake of other appliance

J

12 in (30 cm)

Clearance to non-mechanical air supply inlet to building, or the combustion air 

inlet to any appliance.

K

24 in (61 cm)

Clearance above roof line for vertical terminations.

L

7 ft (2.13 m)

Clearance above paved sidewalk or paved driveway located on public property.

Air Supply Inlet

Gas Meter

Restriction Zone

(Termination not allowed)

Termination Cap

G

G

Opens

Opens

Opens

D

F

B

B

A

I

H

K

G

G

L

C

E

1. Do  not  terminate  the 

vent  in  any  enclosed  or 

semi-enclosed  areas  such 

as  a  carport,  garage, 

attic,  crawlspace,  narrow 

walkway,  closely  fenced 

area,  under  a  sundeck 

or  porch,  or  any  location 

that  can  build  up  a 

concentration  of  fumes 

such as stairwells, covered 

breezeway, etc.

19

Содержание M55-FPIs640

Страница 1: ...LD RESULT IN PROPERTY DAMAGE BODILY INJURY OR EVEN DEATH Contact your building or fire officials about restrictions and installation inspection requirements in your area W A R R A N T Y R E G I S T R...

Страница 2: ...o Locate Your Pellet Appliance 16 Removing Pellet Stove From Pallet 16 Installing the Inset Frame and Levelling 17 Clearances to Combustibles 18 Thermostat Installation 18 Vent Termination Requirement...

Страница 3: ...ove needing to be cleaned daily A low ash fuel may allow longer intervals between cleaning CLINKERING clinkers are silica sand or other impurities in the fuel that will form a hard mass during the bur...

Страница 4: ...15 2015 Under specific test conditions this heater has been shown to deliver heat at rates ranging from 9 200 45 500 Btu hr Emissions Rating Label Serial No DATE OF MANUFACTURE J F M A M J J A S O N...

Страница 5: ...again until you are certain the chimney and its lining have not been damaged OPERATION The door and ash drawer must be kept closed when the unit is in operation to prevent fume spillage and for prope...

Страница 6: ...y suitable measures e g load distributing plate must be taken to achieve it DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING A...

Страница 7: ...pe Residential Pellet Heater 6mm dia Pellets wood corn wheat barley Voltage Current Max Power 110 120 V 4 2 Amps 504 Watts Frequency Hopper Capacity Consumption on Low 60 Hz up to 50 lb 22 7 Kg 1 5 lb...

Страница 8: ...feed settings When pressed all lights on Heat Level Indicator will come on except the one that is the set point Hold Trim Button down and press the UP or DOWN Heat Level Arrow to adjust setting 3 Lig...

Страница 9: ...t operate for the first five minutes after the ON button has been pressed After the ten minutes it will pulse at the same interval as the feed auger When the start up sequence is complete the unit wil...

Страница 10: ...water column 37 42 Pa This can be measured using a Magnahelic pressure gauge once the unit has been running on heat level 5 setting after one hour of burn time This adjustment is necessary for varyin...

Страница 11: ...o adjust this cover either up or down to control the maximum output of 55 000 BTU Lowering the cover position will decrease output and raising it will increase output CAUTION Increasing output too muc...

Страница 12: ...it 3 The agitator locks at the right rotate the top of the agitator towards the back of the firebox to unlock it slide it to the left and lift it out of the burn pot liner 4 Lift the burn pot liner o...

Страница 13: ...use the gasketing may come loose To repair this glue the gasketing on using high temperature fiberglass gasket glue available from your local dealer This is important to maintain an airtight assembly...

Страница 14: ...N CLEAN UP Once you are finished using the pellet appliance for the season unplug the stove for added electrical protection It is very important that the stove be cleaned and serviced as stated above...

Страница 15: ...2 Close up of Front Rail Quick Release Pin Thumb Screw 1 Remove Cast Ash Drawer Front 2 Slide open the Cast Top 3 Lift off Cast Sides 4 Clip Side Rails to unit 5 Attach Front Rail using the quick rele...

Страница 16: ...l units installed in Mobile and Air Tight Homes R2000 or where required by local codes 7 Do not obtain combustion air from an attic garage or any unventilated space Combustion air may be obtained from...

Страница 17: ...e length of the bolts masonry bricks may be placed under the frame 4 Once level position the Insert Frame in the fireplace cavity so that the Surround Panel is flush with the front of the fireplace 5...

Страница 18: ...matically O will drop down t will return to pre and it will restar To Turn Off Stov AUTO OFF mo Pour d marrer qualit de supe carburants App pot de br lure h Pour faire fonct MODE HIGH L tre ajust s L...

Страница 19: ...llowable exterior vent termination locations Table 2 Use in conjunction with Figure 6 for allowable exterior vent termination locations Letter Minimum Clearance Description A 24 in 61 cm Above grass t...

Страница 20: ...mes When connecting to an outside fresh air source do not use plastic or combustible pipe A 3 minimum 76 mm ID inside diameter steel aluminum or copper pipe or ducting should be used The inlet must ha...

Страница 21: ...Chimneys 6 It is necessary to permanently seal any opening between the masonry of Figure 9 Masonry fireplace installation the fireplace and the facing masonry When installing the insert into a masonry...

Страница 22: ...from the fireplace from entering the chimney which will affect proper drafting of appliance Figure 10 Masonry fireplace positive flue installation A qualified installer should evaluate the existing fi...

Страница 23: ...st be supported with sheet metal studs and have no combustible material in the air space All venting for Built In installation must use PL or L venting and be installed with vent manufacturer s recomm...

Страница 24: ...st caused by airflow around the structure Follow vent manufacturer guidelines for installation clearance to combustibles and sealing of venting High temp Sealant must be used when connecting vent pipe...

Страница 25: ...nation Installation Figure 12 Venting horizontally with rise NOTE This venting configuration is only for use with the Built In installation Wall framing Wall thimble Termination cap Vertical section o...

Страница 26: ...PL vent upward from the tee Make sure that you install support brackets to keep the vent straight and secure All joints in the exhaust venting system must be fastened with at least three 3 screws 3 I...

Страница 27: ...in the exhaust venting system must be fastened with at least three 3 screws 3 Install ceiling thimble and secure the flashing as you go through the roof 4 Ensure that the rain cap is approximately 24...

Страница 28: ...If the 3 light is flashing unit may be out of fuel Check the Door and Ash Pan door THEY MUST BE CLOSED TIGHT See section 8 The Fuel will not light Check the fuse on the circuit board If the unit still...

Страница 29: ...require vertical section to move termination into a low pressure zone To reset Circuit Board after a trouble code push the ON OFF button 5 Unit is on but auger motor does not turn at all Check the li...

Страница 30: ...of the Heat Level button make sure the thermostat is calling for heat Call your local dealer for service 10 The stove keeps going out If the stove goes out and leaves fresh unburned fuel in the burn p...

Страница 31: ...Grey Grey Orange Orange White Grey Grey White Blue Yellow Auger Motor White Yellow Vacuum Switch Connect Thermostat Here Brown Brown Blue Purple Yellow Red Thermostat Combustion Blower Black Black Whi...

Страница 32: ...uger Collar with Screw 50 968 14 Auger Motor 2rpm 50 2054 15 Exhaust Motor Capacitor including Strap 50 2053 16 Agitator Drive Shaft with Sprocket 50 1698 17 Motor Drive Sprocket 50 1700 18 Auger Moto...

Страница 33: ...of 2 50 2294 54 Bearings with Mounting Bolts Set of 4 50 2295 55 M55C FPI Milan Empress FPI 2 Amp Small Fuse 50 2302 56 M55C FPI Milan Empress FPI 4 Amp Small Fuse Ignitor 50 2303 57 Agitator Drive B...

Страница 34: ...2276 68 M55C FPI Cast Ash Door Chestnut 50 2282 68 M55C FPI Cast Ash Door DB 50 2299 69 M55C FPI Cast Surround Trim Only PD 50 2272 69 M55C FPI Cast Surround Trim Only Beach 50 2278 69 M55C FPI Cast...

Страница 35: ...Parts Diagram Components 6 48 1 2 3 4 8 23 14 10 11 15 9 29 21 7 42 24 12 54 25 17 16 18 40 5 22 45 41 49 47 52 53 13 19 20 37 35...

Страница 36: ...Parts Diagram Steel 69 70 38 28 57 26 27 63 5 62 61 36 51 59 66 67 68 64 65 30 37 39 44 36...

Страница 37: ...Notes 37...

Страница 38: ...Notes 38...

Страница 39: ...cluding serial number Exclusions An expanded list of exclusions is available at www enviro com help warranty html This warranty does not cover Damage as a result of improper usage or abuse Damage caus...

Страница 40: ..._____________________ DATE OF PURCHASE _____________ dd mm yyyy DATE OF INSTALLATION ___________ dd mm yyyy MAGNEHELIC AT INSTALL ___________________ INSTALLER S SIGNATURE ____________________________...

Отзывы: