CODE INDICATION
ON/OFF LED = ON
ON/OFF = OFF
DEFAULT
SETTING
FUNCTION
LED
SETTING
LED
A
6
Safety1 sensor is a Normally Closed input
(N.C.)
Safety1 sensor is
Normally Open input (N.O.)
LED OFF
– Safety1 is
Normally Open
A
7
Safety2 independent
of Act’n1
Safety2 is ON = door holds
Safety2 is OFF = door opens
Safety2 works with
Act’n1
Safety2 &
Act’n1 both ON
= door holds
If Safety2 is OFF = door opens
If
Act’n1 is OFF = door closes.
LED OFF
Safety2 works
with Act’n1.
A
8
Only for Fire door mode in California.
Manually pulling the door closed while it
is fully open will close the door ignoring all
activation triggers including Hold Open.
Turning to OFF will reset this mode.
Door will not shut when
manually pulled closed
LED OFF
A
9
Safety monitoring ON for SM1.
This monitors SAFETY1 input.
See safety monitoring wiring and notes
Safety Monitoring OFF
for SM1
LED OFF
– No safety
monitoring
A
A
Safety monitoring ON for SM2A.
This monitors SAFETY2 input.
See safety monitoring wiring and notes
Safety Monitoring OFF
for SM2A
LED OFF
– No safety
monitoring
When setting up A8, it is important to follow the steps below:
1. Turn the overload all the way down (counter clock wise for Analog Potentiometer)
2. Make sure Back Check speed is slow enough that it will not trigger the overload
while the door is fully open.
RESET TO DEFAULT SETTING
- Pressing both SET and PASS buttons for 5 seconds
8.0 CONTROL BOARD PROGRAMMING