background image

 
 

 

 

 

                                                                                                      7/22 

AMF 3.1 USER MANUAL 

 Selection Button: 

 

While in normal operation this button has the same function as the button above. 

 

While  in  parameter menu,  after  pressing  the  Enter  Button  and  selecting  a  parameter  to  edit,  the  desired 

digit can be selected by using this button, each press will shift the selected digit to the right. 

 

 

OPERATION MODES 

 

Automatic  Operation  Modes:

  When  the  Auto  Button 

  is  pressed  the  Generator  will  enter  the  Automatic 

Operation Mode. In this mode, the 3 phase Mains is constantly monitored against the limits set by the parameter 

values shown below.  

P036 

Mains Under Voltage 

P037 

Mains Over Voltage 

 

 

 

When  the  Mains  is  normal,  the  Load  is  supplied  by  the  Mains.  If  the  monitored  values  of  the  Mains  are 

outside the limits set by the related parameters and the time period specified by the 

“P039 – Mains Failure Delay 

Timer” has passed, it means there is a Mains failure. In this case the Mains contactor is opened and the Generator 

is started. 

Once the Generator has started, the unit will wait for the time period set by the “P018 – General Failure 

Delay  Timer”  and  will  check  for  any  failures.  Then,  after  waiting  for  the  time  period  set  by  “P006  –  Generator 

Contact Delay Timer”, the Generator contactor will be closed and the Load is transferred to the Generator. 

Once the monitored values of the Mains are back and stays within the limits set by the related parameters 

for  the  time 

period  set  by  the  “P005  –  Mains  Contact  Delay  Timer”,  the  Mains  contactor  will  be  closed  and  the 

Load is transferred to the Mains. In the case where the Generator has supplied the Load since the engine started, 

the engine will be 

cooled down for the time period set by “P007 – Engine Cool-down Timer”. If the Generator has 

not  supplied  the  Load  since  the  engine  started,  the  Generator  will  be  stopped  without  cooling  down.  In  the 

Automatic  operation  mode,  if  the  AMF  unit  is  receiving  a  signal  that  the  Generator  is  running  although  it  is  not 

supposed to, the AMF will try to stop the Generator. 

 

Test Operation Mode: 

When the TEST Button is pressed the Generator enters the Test operation mode and the 

Generator will start without checking the Mains. In this mode the Generator Contactor Status Button 

 and the 

Mains Contactor Status Button 

 will become active. If the Generator is running and the Generator Status LED 

is constantly lit, the Generator contactor can be checked using the Generator Contactor Status Button 

 as long 

as  the  Mains  contactor  is  open.  The  Generator  Contactor  Status  Button 

  will  energize  the  GCB  if  it  is  de-

energized  and  will  transfer  the  Load  to  the  Generator.  If  the  GCB  is  already  energized,  pressing  the  Generator 

Contactor Status Button will idle the Load. The same situation is applicable for the Mains Contactor Status Button 

also. If the Mains status LED is constantly lit and the Generator contactor is open, the Load can be transferred to 

P040 

Mains Under Frequency 

P041 

Mains Over Frequency 

Содержание AMF 3.1

Страница 1: ...AMF 3 1 EN K K 01 KO AMF 3 1 User Manual...

Страница 2: ...4 Front Panel 5 Rear Panel 9 Terminal Connections 9 Alarm Codes Descriptions 11 Interface Structure 14 MENU SCREEN STRUCTURE 16 P2 Alarm Log Screen 18 P3 Maintenance Timers Screen 18 Digital Input Fu...

Страница 3: ...ion modes Measurement instruments which reduce the panel cost Time stamped log of the last 15 failures Record of engine running hours and indicate when maintenance is needed Manual control of the MCB...

Страница 4: ...4 22 AMF 3 1 USER MANUAL Connection Diagram...

Страница 5: ...nd the Load is fed through the Generator The Mains contactor must be opened in order to close the Generator contactor Generator Contactor Status LED 3 Indicates the GCB status If the GCB output termin...

Страница 6: ...oltage Start Stop Over Current Fuel Level Charge Voltage Low Oil Pressure Coolant Level Engine Over Heat Battery Voltage Mains Contactor Generator Contactor Emergency Stop and Maintenance Time LED s c...

Страница 7: ...by the related parameters for the time period set by the P005 Mains Contact Delay Timer the Mains contactor will be closed and the Load is transferred to the Mains In the case where the Generator has...

Страница 8: ...ly stopped If the Load has never been transferred to the Generator then it will be stopped without being cooled down By pressing the OFF button twice the Generator will be stopped without being cooled...

Страница 9: ...s output is Normally Open 250Vac 10A 7 COM 2 The common input of Terminals No 6 and No 8 GCB 250Vac 10A Caution In order to enable the related Terminals to COM 2 this input must NOT be left empty 8 GE...

Страница 10: ...Caution If a battery connection is NOT made to COM 7 the related digital inputs will not be operational 28 AUX INPUT 1 1 st digital input Can be configured via parameters P206 P211 29 AUX INPUT 2 2 n...

Страница 11: ...d attempts to stop the engine F24 It indicates Overcurrent alarm This alarm is indicated when the total current is more than P272 Over Current Failure Value F22 F23 It indicates Fuel Level Alarm F22 i...

Страница 12: ...Failure Input 3 Alarm This alarm is active when the digital input set for External Alarm Input 3 becomes active F34 It indicates Aux Failure Input 4 Alarm This alarm is active when the digital input s...

Страница 13: ...ill wait in the system Once the operator manually removes the alarm the auto acknowledge counter will restart and acknowledge alarms until it reaches the limit set by parameter P051 again The table be...

Страница 14: ...Emergency situation P233 F16 F17 F21 F31 F32 F33 F34 F35 F42 F43 F45 Depends on the function assigned to Aux Input 6 Oil Switch High Temperature Switch Low Coolant Level Aux Alarm 1 2 3 4 5 MCB Feedb...

Страница 15: ...Note 1 1st Row Abbreviation for Frequency 2nd Row Mains R Phase Frequency Hz Please see Note 1 1st Row Abbreviation for Frequency 2nd Row Generator U Phase Frequency Hz Please see Note 1 1st Row Abbre...

Страница 16: ...age Please see Note 1 1st Row Abbreviation for Fuel Level 2nd Row Fuel Level While on this screen pressing the up button will navigate to the screen shown on the top of this table VR N Voltage While o...

Страница 17: ...screen If the password entry is correct the screen below will appear In order to view edit a parameter the parameter number must be entered first The display indicating 000 shows the parameter number...

Страница 18: ...ime stamp information can be seen by pressing the Down button The screen similar to the one shown below will appear The total running hours when the at the time the alarm occurred is displayed on this...

Страница 19: ...indicating AUX INPUT on the back panel are the digital inputs of the panel These inputs are optically isolated COM 7 is the common for auxiliary inputs 1 2 3 and 4 COM 8 is the common for auxiliary i...

Страница 20: ...tem will not control this contactor 18 Earthquake This function is to be assigned if there is an earthquake sensor in the system This is a Level 5 alarm independent from the system 19 Keyboard Disable...

Страница 21: ...tput this function should be selcted 1 Engine Running If the engine has started and alarm delay time has passed this output will be activated 2 AUTO Ready If the panel is in AUTO mode this output will...

Страница 22: ...lecom Running This output is activated once the battery voltage drops below the limit set by P26 and is deactivated once the voltage reaches the limit set by P27 There is a 5 second delay between leve...

Отзывы: