background image

 
 

 

 

 

                                                                                                      2/22 

AMF 3.1 USER MANUAL 

Table of Contents 

 

General Descriptions ............................................................................................................................................................................... 3

 

Connection Diagram ............................................................................................................................................................................... 4

 

Front Panel .............................................................................................................................................................................................. 5

 

Rear Panel ............................................................................................................................................................................................... 9

 

Terminal Connections ......................................................................................................................................................................... 9

 

Alarm Codes & Descriptions ................................................................................................................................................................ 11

 

Interface Structure ................................................................................................................................................................................. 14

 

MENU SCREEN STRUCTURE ........................................................................................................................................................... 16

 

P2-Alarm Log Screen ........................................................................................................................................................................ 18

 

P3-Maintenance Timers Screen ......................................................................................................................................................... 18

 

Digital Input Functions & Descriptions ................................................................................................................................................ 19

 

Digital Output Functions & Descriptions .............................................................................................................................................. 21

 

Document Version................................................................................................................................................................................. 22

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Содержание AMF 3.1

Страница 1: ...AMF 3 1 EN K K 01 KO AMF 3 1 User Manual...

Страница 2: ...4 Front Panel 5 Rear Panel 9 Terminal Connections 9 Alarm Codes Descriptions 11 Interface Structure 14 MENU SCREEN STRUCTURE 16 P2 Alarm Log Screen 18 P3 Maintenance Timers Screen 18 Digital Input Fu...

Страница 3: ...ion modes Measurement instruments which reduce the panel cost Time stamped log of the last 15 failures Record of engine running hours and indicate when maintenance is needed Manual control of the MCB...

Страница 4: ...4 22 AMF 3 1 USER MANUAL Connection Diagram...

Страница 5: ...nd the Load is fed through the Generator The Mains contactor must be opened in order to close the Generator contactor Generator Contactor Status LED 3 Indicates the GCB status If the GCB output termin...

Страница 6: ...oltage Start Stop Over Current Fuel Level Charge Voltage Low Oil Pressure Coolant Level Engine Over Heat Battery Voltage Mains Contactor Generator Contactor Emergency Stop and Maintenance Time LED s c...

Страница 7: ...by the related parameters for the time period set by the P005 Mains Contact Delay Timer the Mains contactor will be closed and the Load is transferred to the Mains In the case where the Generator has...

Страница 8: ...ly stopped If the Load has never been transferred to the Generator then it will be stopped without being cooled down By pressing the OFF button twice the Generator will be stopped without being cooled...

Страница 9: ...s output is Normally Open 250Vac 10A 7 COM 2 The common input of Terminals No 6 and No 8 GCB 250Vac 10A Caution In order to enable the related Terminals to COM 2 this input must NOT be left empty 8 GE...

Страница 10: ...Caution If a battery connection is NOT made to COM 7 the related digital inputs will not be operational 28 AUX INPUT 1 1 st digital input Can be configured via parameters P206 P211 29 AUX INPUT 2 2 n...

Страница 11: ...d attempts to stop the engine F24 It indicates Overcurrent alarm This alarm is indicated when the total current is more than P272 Over Current Failure Value F22 F23 It indicates Fuel Level Alarm F22 i...

Страница 12: ...Failure Input 3 Alarm This alarm is active when the digital input set for External Alarm Input 3 becomes active F34 It indicates Aux Failure Input 4 Alarm This alarm is active when the digital input s...

Страница 13: ...ill wait in the system Once the operator manually removes the alarm the auto acknowledge counter will restart and acknowledge alarms until it reaches the limit set by parameter P051 again The table be...

Страница 14: ...Emergency situation P233 F16 F17 F21 F31 F32 F33 F34 F35 F42 F43 F45 Depends on the function assigned to Aux Input 6 Oil Switch High Temperature Switch Low Coolant Level Aux Alarm 1 2 3 4 5 MCB Feedb...

Страница 15: ...Note 1 1st Row Abbreviation for Frequency 2nd Row Mains R Phase Frequency Hz Please see Note 1 1st Row Abbreviation for Frequency 2nd Row Generator U Phase Frequency Hz Please see Note 1 1st Row Abbre...

Страница 16: ...age Please see Note 1 1st Row Abbreviation for Fuel Level 2nd Row Fuel Level While on this screen pressing the up button will navigate to the screen shown on the top of this table VR N Voltage While o...

Страница 17: ...screen If the password entry is correct the screen below will appear In order to view edit a parameter the parameter number must be entered first The display indicating 000 shows the parameter number...

Страница 18: ...ime stamp information can be seen by pressing the Down button The screen similar to the one shown below will appear The total running hours when the at the time the alarm occurred is displayed on this...

Страница 19: ...indicating AUX INPUT on the back panel are the digital inputs of the panel These inputs are optically isolated COM 7 is the common for auxiliary inputs 1 2 3 and 4 COM 8 is the common for auxiliary i...

Страница 20: ...tem will not control this contactor 18 Earthquake This function is to be assigned if there is an earthquake sensor in the system This is a Level 5 alarm independent from the system 19 Keyboard Disable...

Страница 21: ...tput this function should be selcted 1 Engine Running If the engine has started and alarm delay time has passed this output will be activated 2 AUTO Ready If the panel is in AUTO mode this output will...

Страница 22: ...lecom Running This output is activated once the battery voltage drops below the limit set by P26 and is deactivated once the voltage reaches the limit set by P27 There is a 5 second delay between leve...