12/22
AMF 3.1 USER MANUAL
F19
F20
It indicates “Low Battery Voltage Alarm”.
F20 is displayed when the battery voltage is less than or more than the set values. (see:
P47: Battery Voltage Failure Lower Limit, P48: Battery Voltage Failure Upper Limit).
F43
It indicates “Mains Circuit Breaker Feedback Failure Alarm”.
F43 is displayed when the digital input set for MCB Contact Feedback does not become
active after the breaker is energized.
F42
It indicates “Generator Circuit Breaker Feedback Failure Alarm”.
F42 is displayed when the digital input set for GCB Contact Feedback does not become
active after the breaker is energized.
F44
It indicates “Emergency Stop Alarm”. F44 is displayed when the digital input set for
Emergency Stop becomes active.
It indicates “Maintenance Time Passed” alarm.
This LED is lit when “P329: Periodic Engine Maintenance Timer Set Value and “P330:
Periodic Maintenance Timer Value expire.
F31
It indicates “Aux. Failure Input 1 Alarm”.
This alarm is active when the digital input set for External Alarm Input 1 becomes active.
F32
It indicates “Aux. Failure Input 2 Alarm”.
This alarm is active when the digital input set for External Alarm Input 2 becomes active.
F33
It indicates “Aux. Failure Input 3 Alarm”.
This alarm is active when the digital input set for External Alarm Input 3 becomes active.
F34
It indicates “Aux. Failure Input 4 Alarm”.
This alarm is active when the digital input set for External Alarm Input 4 becomes active.
F35
It indicates “Aux. Failure Input 5 Alarm”.
This alarm is active when the digital input set for External Alarm Input 5 becomes active.
F26
It indicates “High KW Alarm”.
This alarm is active when the measured kW value is equal to or more than P277: KW
Failure Value.
F27
It
indicates “High KVA Alarm”.
This alarm is active when the measured kVA value is equal to or more than P292: KVA
Alarm Value.
F28
It indicates “High KVAR Alarm”.
This alarm is active when the measured kVAR value is equal to or more than P282-
KVar Failure Value.
F29
It indicates “Power Factor Alarm”.
This alarm is active when the measured Power Factor value is equal to or more than
P287: Power Factor Failure Value.
F38
It indicates “Seismic Alarm.”
This alarm is active when the digital input set for Earthquake Sensor becomes active.
F46
It indicates “Oil Pressure Sensor Failure Alarm”.
When there is a oil pressure sensor, the reason of the failure may be that the sensor
has failed, been damaged or been removed.
F47
It indicates “Temperature Sensor Failure Alarm”.
When there is a temperature sensor, the reason of the failure may be that the sensor
has failed, been damaged or been removed.
Содержание AMF 3.1
Страница 1: ...AMF 3 1 EN K K 01 KO AMF 3 1 User Manual...
Страница 4: ...4 22 AMF 3 1 USER MANUAL Connection Diagram...