A
G-TRAC2
IOM-25
30 of 42
Mar 99 R7
TE6000 Discharge Sensor Self-Test
If the discharge sensor resistance is greater than 4000-ohms or less than 880-ohms, the unit will lock out either on low limit
or bad temperature sensor. The G-TRAC2 will not operate with a bad discharge sensor. If the G-TRAC2 locks out due to an
open discharge sensor LED 3 will flash rapidly.
Sensor Resistance Chart for TE 6100-960 and TE 6000-960
°C
°F
Resistance
°C
°F
Resistance
°C
°F
Resistance
-40
-40
602-605
18.3
65
983
48.9
120
1234
-34.4
-30
633
20
68
996
54.4
130
1269
-28.9
-20
665
20.6
69
1000.7
60
140
1333
-23.3
-10
698
21.1
70
1005
65.5
150
1365
-17.8
0
732
23.9
75
1026.5
71.1
160
1437
-12.2
10
768
26.7
80
1048
76.7
170
1491
-8.7
20
804
29.4
85
1070
82.2
180
1546
-1.1
30
842
32.2
90
1092
87.7
190
1602
4.4
40
881
35.6
95
1116
93.3
200
1659
10
50
921
37.8
100
1139
98.8
210
1718
12.8
55
941.5
43.3
110
1186
100
212
1778
*Reference resistance is 1035 ohms at 77°F. Resistance tolerances are ±0.05 to 0.15% at 77°F.
*Temperature range +32 to +104°F.
(TE 6100-960 pot is 53C3, 500R, 7/8 by ¼ shaft.)
Discharge Sensor Calibration
NOTE:
These controls are calibrated at the factory and in most instances field calibration is not necessary.
The discharge sensor is used for both temperature control and low limit safety control. For that reason
it is VERY important
that this calibration step be PROPERLY done
. The G-TRAC2 has two calibration pots. DSEN CAL is used to calibrate the
discharge sensor, and DSP CAL is used to calibrate the discharge set point.
1.
Accurately measure the discharge air temperature at the temperature sensor.
NOTE:
The sensor should be located in a stable, non-changing temperature location between 5 and 30ºC.
Calibration at other temperatures will not produce as accurate a result.
2.
Read the G-TRAC2 discharge temperature by reading the DC voltage across spade connector terminals “DTEMP”
and “COMMON”. The readings are based on 10ºC per volt.
(See Discharge Temperature Readout for table.)
3.
If required, adjust DSEN CAL until the two readings agree.
Discharge Set-Point Calibration
1.
Record the settings of dipswitches 1, 2, and 3.
2.
Turn off dipswitch 1, 2, and 3 and remove wire to terminal OR and K. This eliminates all resets, leaving only the
base set point value across the test points.
3.
Set discharge set point to 20ºC. The base set point in ºC is the DC volts across test points “SPC” to “COMMON”
multiplied by 10°C.
4. NOTE:
There are different calibration procedures for JOHNSON TE 6100 and the G-TRAC2 face mounted set point.
Select the applicable one and go to point 4-1 or 4-2.