A
G-TRAC2
IOM-25
33 of 42
Mar 99 R7
XXIII. BURNER SET UP
Operator Control Rules
The G-TRAC2 provides separate independent control loops for the gas and air operators. Each operator has a position
feedback set point and deadband. The control deadband is the allowable operator position error
(actual position versus set
point)
before the operator is repositioned. The calculated position set point is determined by a combination of pot settings
and the current firing rate. The main job of the deadband is to reduce the number of operator start/stop steps.
The G-TRAC2 follows three basic rules for moving the operators.
1.
Once an operator is stopped, do not start it again until its position error gets too large.
2.
Once an operator is moving, stop it at the position set point.
(Centre of deadband.)
3.
Do not let one operator get ahead of the other. Different operator model’s stroke speeds and/or stroke size result in
different operator speeds. If one operator gets too far ahead, stop it and wait for the other operator to catch up.
Manual Service Mode
When the service dipswitch A-5 and the fan switch are on, the G-TRAC2 is placed into the manual service mode. In this
mode, the burner will cycle on and can be held at any firing rate set with the manual
service pot
.
The supply air fan will start 64 seconds after the flame starts.
The G-TRAC2 will not lock the unit out on flame failure.
The low limit is still active in the manual service mode.
The operation of the blower depends upon a combination of conditions.
1.
Service mode. Fan switch on and dipswitch A-4 off.
The blower will start 64 seconds after the main flame comes on.
The outside damper contact makes as soon as the main flame comes on.
2.
Service mode. Fan switch on and dipswitch A-4 on
. The blower will start 64 seconds after the fan switch is made. The
blower will only wait for the burner to start if the discharge temperature is below 40ºF. The outside damper contacts
will close as soon as the blower timer starts.
IMPORTANT USAGE NOTES REGARDING THE SERVICE POT
The unit must not be left in the service mode.
When leaving the unit make sure that the dipswitch A-5 for service is
OFF.
When the service switch is on the burner will not cycle off.
An irregular flashing of LED 2 indicates that the unit is in service mode.
(Dipswitch A-5 is still
ON
.)