A
G-TRAC2
IOM-25
20 of 42
Mar 99 R7
Same as Diagram A but wider reset range because Pot
5 set at 5.
Diagram C
Discharge Operating Range
Absolute lowest
allowed discharge set
point
Lower reset limit
Manual Set point
Ex 70°F
Upper reset limit
Absolute highest
allowed discharge
set point
120°F
48°F
Discharge Operating Range
Same as Diagram C except set point set low enough with wide reset range
so bottom end of reset is cut off by absolute lowest limit.
Discharge Operating Range
Diagram D
Absolute lowest
allowed discharge set
point
Lower reset
limit
Manual Set point
Ex 55°F
Upper reset limit
Absolute highest
allowed discharge
set point
120°F
48°F
Lower reset limit
same as absolute
discharge set point
Control cannot reset
into this area
(below
48°F)
.