XIV. TEMPERATURE CONTROL – GENERAL OVERVIEW
The G-TRAC2 is primarily a “discharge air control”. Optional discharge reset devices and night heat packages are available.
Refer to unit wiring diagram and/or GTRAC-2 dipswitch label to see how your unit is equipped.
Wires to G-TRAC2
OPTION
M,S,U
Remote Set Point
VXYZ
Room RA Reset and/or Night Heat
Resistor Network and +/-
Sensor XZ Ambient Reset – BMS Reset
XV. THE MASTER SET-POINT
As a
set point
, the G-TRAC2 is designed to use either:
The set point mounted on the face of the G-TRAC2
(range of 12.7-37.8°C or 55-100°F)
. If the G-TRAC2 face mounted set
point is used, terminals ‘SP and S’ must be jumped, or;
The Johnson TE 6100-960 set point
(range of 50-85°F and usually remote mounted)
. If the TE 6100-960 is used as a set
point, ‘S to SP’ is not jumpered and the TE 6100 must be wired as follows:
TE 6100 Wires
G-TRAC2 Terminals
Violet
(not used, sensor)
Blue
M
Orange
S
Grey
U
Red
(not used)
Q
(No jumper S-SP)
P
XVI. INDUCED VOLTAGE ON REMOTE CONTROL WIRING
Factory calibration will satisfy most applications unless resistance from long wiring runs or induced voltage on the remote
wiring cause it to be out of calibration.
(To check for induced voltages, disconnect the entire field wiring in question from the
G-TRAC2 while the unit is operating, and check for AC volts across each questionable wire and ground.)
XVII. NIGHT HEAT THERMOSTATS
The GTRAC-2 control can be activated to control room heat at night. This requires the GTRAC-2 be configured for night
operation and have a configured and equipped room thermostat. If there is a modulating or single stage room thermostat
connected to terminals “X, V, Y, and Z”, the night heat function will be activated when terminal “K” is powered.
XVIII. ROOM RESET THERMOSTAT OPTIONS
The actual discharge temperature of the unit can be electronically adjusted or reset when the actual room temperature
deviates from the required room temperature.
(Refer to these sections for a fuller understanding of the room thermostat in
your systems application)
:
Day/Night Operation
(option)
also refers to night information above.
Temperature Control
information above and below.
Modulating Room Reset
(option)
using TE 6100 thermostat below.
Make/Break Thermostats
(option)
using a standard room thermostat below.
TE 6000 Sensor
Discharge Air
Sensor