A
G-TRAC2
IOM-25
41 of 42
Mar 99 R7
NOTE:
If the following information is not recorded on the G-TRAC2 configuration label attached to the control
cabinet wall, any time you see any G-TRAC2 equipped unit, you should record these voltages on the wall of
the control cabinet for later use in case the G-TRAC2 ever fails.
Before changing a G-TRAC2, if possible you should have the unit in operation and record the following information so that
you may make the change quickly and avoid a time consuming combustion set up. If the information is already recorded on
a label on the unit and the G-TRAC2 is operable it is advisable to recheck the values.
If you follow the steps below using the recorded values, the burner set up should not change significantly from the existing
G-TRAC2.
On any G-TRAC2 change
(if the G-TRAC2 is operable)
, before disconnecting any of the wiring operate the unit and record
the following information.
Using a DC voltmeter record the following:
1.
Set the dipswitches on the new G-TRAC2 to match those on the existing one. There are 3 sets of dipswitches on the
new G-TRAC2. On the top front there is an open set, through the slot under the set point knob there is another set,
and on the latest revision there is a set of dip switches on the back near the top.
2.
Set dipswitch A-5
(on the top set of switches)
ON to place the G-TRAC2 into the
service mode
.
3.
Measure and record the following values to at least 1/10-volt accuracy.
4.
Take the burner to high fire – record feedback DC voltage across “PL and PA”. Also
record the values on the unit
for future reference.
5.
Take the burner to low fire – record feedback DC voltage across “PL and PA” _____ and record feedback DC voltage
across “PL and PG” _____. Also
record the values on the unit
for future reference.
6.
With the unit at low fire, turn the unit off.
7.
Install the new board.
8.
After the new board is installed, turn on dipswitch A-5 to place the new G-TRAC2 into the service mode. Take the
unit to high fire. Adjust the
high fire air pot
until the voltage across “PL and PA” matches the value recorded
above.
9.
Adjust the low fire pot to get the “PL and PG” values recorded above.
10.
Take the unit to low fire. Adjust the
low fire air pot
until the voltage across “PL and PA” match those recorded
above.
11.
Recheck the above values. Try to be very accurate.
(Less than
1
/
10
of a volt.)
12.
If the combustion was correct before it should still be correct.
13.
Turn off dipswitch A-5 to put unit into “AUTO” mode.