A
G-TRAC2
IOM-25
16 of 42
Mar 99 R7
2.
Heat Required LED ON
Upon a call for heat, the “Heat Required” LED light will come on.
3.
Pre-Purge Light
PRE-PURGE LITE ON
When the combustion air actuator is in the correct position, the air-proving switch will close and the “pre-purge” light and
timer will start. When the burner is pre-purging, the “pre-purge” light will remain ‘on’. After the pre-purge cycle is
complete, the combustion air damper has moved to the light-off position, and if required, the gas valve has also been
driven to the light off position:
The “pre-purge” light turns off,
The “Burner On” light comes on,
The set of relay contacts between terminals "AS and 2" close
The ignition control device is energized.
The flame supervision device energizes the pilot gas valve and spark. If the pilot lights and the flame supervision device
prove the pilot flame, the flame supervision device then energizes the main gas valve.
“DM and DM” contacts will close at this stage to open the dampers, if they are wired through this optional contact.
The “Supply Blower On” light may flash in a long and short pattern, while the heat exchanger is warming up
NOTE:
If at any time the combustion air proving switch opens while the burner is firing, the burner is shut off and
the G-TRAC2 will go to flame failure lockout. (Combustion fan will stop in a few minutes). The “Flame
Failure” light will flash and a signal will be on terminal “LK”. The same voltage will be at terminal C as
what is input at terminal A.
If the main flame lit, about 15 seconds later the G-TRAC2 interrupts the pilot valve power. The combustion air damper and
the gas valve position modulate to maintain the required discharge temperature while maintaining the correct air and fuel
ratios for proper combustion. This is
Normal Burner Operation
.
When the discharge air temperature is satisfied, the combustion air blower continues to run in a “maintain purge” mode
(with the combustion air actuator in a partially open position)
to allow immediate re-ignition if there is another heat call
within five minutes. The gas actuator should be at low fire position as that is where the burner cycled off as part of its
normal operation.
At any time during the above, if the heat switch and/or fan switch is turned off the burner is cycled off. The combustion fan
continues to run in a “cool down mode” with the air damper at the “maintain purge” position
(partially open)
for 45
seconds.