HF1 Hz (Hz)
— Range:
60.02
to
66
Certified Range:
60.1
to
66
Default:
60.50
HF1 time (s)
— Range:
0.16
to
1000
Certified Range:
0.16
to
1000
Default:
0.16
Enter service
— Range:
Disabled
or
Enabled
Default:
Enabled
Enter service HV (pu)
— Range:
0.88
to
1.1
Default:
1.050
Enter service LV (pu)
— Range:
0.88
to
1.1
Default:
0.917
Enter service HF (Hz)
— Range:
55
to
66
Default:
60.10
Enter service LF (Hz)
— Range:
55
to
66
Default:
59.50
Enter service delay (s)
— Range:
0
to
1600
Default:
300
Random delay (s)
— Range:
0
to
1000
Default:
0
Enter service ramp time (s)
— Range:
0
to
1000
Default:
300
PF export
— Range:
Disabled
or
Enabled
Default:
Disabled
PF import
— Range:
Disabled
or
Enabled
Default:
Disabled
Export limit
— Range:
Disabled
or
Enabled
Default:
Disabled
Export limit (pu)
— Range:
0
to
1
Default:
1.000
Constant Vars
— Range:
Disabled
or
Enabled
Default:
Disabled
Constant Vars setpoint (pu)
— Range:
–1
to
1
Default:
0.000
Export ramp (pu/s)
— Range:
0.01
to
1
Default:
1.000
PF export setpoint (pu)
— Range:
0.4
to
1
Default:
1.000
PF import setpoint (pu)
— Range:
0.4
to
1
Default:
1.000