900-00277-01-001 Rev A
47
Operation
Start on high load (V)
— Range:
Disabled
or
Enabled
. Default:
Disabled
.
This item allows AGS to start the generator due to a high inverter load. See page 53.
Start kW (kW)
— Range:
0
to
8
. Default:
5.0
.
The load size above which AGS will start the generator. See page 53.
Stop kW (kW)
— Range:
0
to
8
. Default:
2.0
.
The load size below which AGS will stop the generator. See page 53.
High load start delay (m)
— Range:
0
to
90
. Default:
1
.
The delay in minutes before AGS starts the generator due to high load. See page 53.
Quiet time
— Range:
Disabled
or
Enabled
. Default:
Disabled
.
This item restricts AGS from starting the generator automatically during certain hours. See page 53.
Quiet time start
— Range:
12:00 AM
to
11:59 PM
. Default:
10:00 PM
.
The beginning of the scheduled period that restricts automatic start. See page 53.
Quiet time stop
— Range:
12:00 AM
to
11:59 PM
. Default:
05:00 AM
.
The end of the scheduled period that restricts automatic start. See page 53.
Exercise
— Range:
Disabled
or
Enabled
. Default:
Disabled
.
This item starts the generator periodically regardless of other conditions. See page 53.
Exercise day
— Range:
Sunday
to
Saturday
. Default:
Sunday
.
The scheduled day for automatic generator exercise. See page 53.
Exercise start
— Range:
12:00 AM
to
11:59 PM
. Default:
04:00 PM
.
The scheduled time for automatic generator exercise. See page 53.
Exercise duration
— Range:
5 minutes
,
15 minutes
, or
30 minutes
. Default:
15 minutes
.
The scheduled length of the exercise period. See page 53.