900-00277-01-001 Rev A
95
Specifications
Table 16
Grid Protection Settings (HECO and ISO-NE)
Range of
Adjustment
Certified
Range
HECO 14H-2018
ISO NE-2018
ISO NE-2021
Parameter
Min
Max
Min
Max
HF1 Hz (Hz)
60.02
66.00
60.1
66.00
63.00
61.20
61.20
HF1 time (s)
0.16
1000.00
0.16
1000.00
21.00
300
300
HF2 Hz (Hz)
60.02
66.00
60.1
66.00
65
62
62
HF2 time (s)
0.16
1000.00
0.16
1000.00
0.16
0.16
0.16
Freq Droop
Disabled Enabled
n/a
n/a
Enabled Disabled Enabled
Freq Droop OF
deadband (Hz)
0.000 1.000
0.000
1.000
0.036
0.036
0.036
Freq Droop UF
deadband (Hz)
0.000 1.000
0.017 1
1.000
8
0.036 0.036
Freq Droop OF ratio
0.020
0.070
0.02
0.07
0.040
0.050
0.050
Freq Droop UF ratio
0.020
0.070
0.02
0.07
0.040
0.050
0.050
Freq Droop response
time (s)
0.20 10.00 5 5
0.50
5.00
5.00
Freq Droop PMin (%)
–100.0
100.0
n/a
n/a
0.0
0.0
0.0
Watt/VAr
9
Disabled
Enabled
n/a
n/a
Disabled Disabled Disabled
Watt/VAr 1 power (pu)
–1.000
0.000
n/a
n/a
–1.000
–1.000
–1.000
Watt/VAr 1 reactive
power (pu)
–0.500 0.500
n/a
n/a
0.440
0.440
0.440
Watt/VAr 2 power (pu)
–1.000
0.000
n/a
n/a
–0.500
–0.500
–0.500
Watt/VAr 2 reactive
power (pu)
–0.500 0.500
n/a
n/a
0.000
0.000
0.000
Watt/VAr 3 power (pu)
–1.000
0.000
n/a
n/a
–0.200
–0.200
–0.200
Watt/VAr 3 reactive
power (pu)
–0.500 0.500
n/a
n/a
0.000
0.000
0.000
Watt/VAr 4 power (pu)
0.000
1.000
n/a
n/a
0.200
0.200
0.200
Watt/VAr 4 reactive
power (pu)
–0.500 0.500
n/a
n/a
0.000
0.000
0.000
Watt/VAr 5 power (pu)
0.000
1.000
n/a
n/a
0.500
0.500
0.500
Watt/VAr 5 reactive
power (pu)
–0.500 0.500
n/a
n/a
0.000
0.000
0.000
Watt/VAr 6 power (pu)
0.000
1.000
n/a
n/a
1.000
1.000
1.000
Watt/VAr 6 reactive
power (pu)
–0.500 0.500
n/a
n/a
–0.440
–0.440
–0.440
Enter service
Disabled Enabled
n/a
n/a
Enabled
Enabled
Enabled
Enter service HV (pu)
0.880
1.100
n/a
n/a
1.100
1.100
1.050
Enter service LV (pu)
0.880
1.100
n/a
n/a
0.880
0.880
0.917
Enter service HF (Hz)
55.00
66.00
n/a
n/a
60.10
61.20
60.10
Enter service LF (Hz)
55.00
66.00
n/a
n/a
59.90
58.50
59.50
Enter service delay (s)
0
1600
n/a
n/a
300
300
300
Random delay (s)
0
1000
n/a
n/a
0
0
0
Enter service
ramp time (s)
1 1000
1
1000 303
10
50 300
8
Setting dBuf to 1.000 Hz is the limit of the range of adjustment in this inverter model. Setting the value to this limit partially disables
frequency-droop under-frequency response. HECO 14H does not require under frequency response, see Figure 4 of HECO 14H, where
frequency response is flat below 60 Hz.
9
Only one of the four VAr functions (
Volt/VAr
,
Watt/VAr
,
Constant PF
,
Constant VAr
) can be enabled at one time.
10
The published requirement in HECO 14H is 0.33 % / s. A value of 1/0.0033 = 303 seconds.