9.1 Troubleshooting Condition Table
Behavior
Part to Check
1. Wall T-Stat (See Section 9.3)
2. Blower/Fan Limit (See Section 9.3)
3. Burner Motor (See Section 9.2)
4. Burner Plug (See Section 9.2)
5. Primary Controller (See Section 9.3)
6. Preheater (See Section 9.3)
1. Burner Motor (See Section 9.2)
2. Primary Controller (See Section 9.3)
3. Cad Cell (See Section 9.3)
4. Tank/Tank Controls (See Section 9.2)
5. Pump/Filter (See Section 9.2)
6. Fuel Quality (See Section 9.2)
7. Transformer/Electrode (See Section
9.3)
8. Air Compressor (See Section 9.2)
03. The burner will not light and fuel pressure is between 3 and
15 PSI (normal) on the pressure gauge at the fuel pump outlet.
1. Go to Behavior Tree 2 Component 6
(See Section 9.2)
1. General Action/Question - Boiler
ONLY! (See Section 9.2)
2. Solenoid Valve (See Section 9.3)
3. Heat Exchanger (See Section 9.2)
4. Damper Tee/Manometer (See
Section 9.2)
5. Air Compressor (See Section 9.2)
6. Pump/Filter (See Section 9.2)
7. Fuel Quality (See Section 9.2)
05. Smoke is seen from the external flue cap or internal
damper door, or the furnace is running rough.
1. Go to Behavior Tree 4
1. Pump/Filter (See Section 9.2)
2. Go to Tree 2 (See Section 9.2)
1. Wall T-Stat (See Section 9.3)
2. Blower/Fan Limit (See Section 9.3)
3. Primary Controller (See Section 9.3)
1. Heat Exchanger (See Section 9.2)
2. Damper Tee/Manometer (See
Section 9.2)
3. Burner Motor (See Section 9.2)
4. Air Compressor (See Section 9.2)
1. Heat Exchanger (See Section 9.2)
2. Go to Behavior Tree 1 (See Section
9.2)
09. The burner cycles on and off every few minutes
01. The furnace does not operate when you set the wall
thermostat to a high temperature.
02. The burner runs around 15 seconds then stops and the red
button of the primary control requires reset.
04. The furnace has a build-up (coke tree) at the front of the
burner in the heat exchanger (combustion chamber) after
running many hours.
06. The unit frequently requires reset in the mornings.
07. The wall thermostat will not shut the burner off.
08. The furnace no longer provides enough heat.
65
Call 1-615-471-5290 for Technical Support
Содержание EL-140H
Страница 2: ......
Страница 51: ...45 Call 1 615 471 5290 for Technical Support ...
Страница 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Страница 91: ...85 Call 1 615 471 5290 for Technical Support ...
Страница 93: ...87 Call 1 615 471 5290 for Technical Support ...
Страница 94: ...88 Call 1 615 471 5290 for Technical Support ...
Страница 95: ...89 Call 1 615 471 5290 for Technical Support ...