1.6 Clearances to Combustible Surfaces
It is of the utmost importance that the installation conform to the minimum
clearances to combustible surfaces (Material made of or surfaced with wood, compressed
paper, plant fibers, plastics, or other material that can ignite and burn, whether flame proofed
or not, or whether plastered or unplastered). Consult applicable codes and regulations for
precedence. Non-compliance to minimum clearances may result in fire, explosion, personal
injury or death. Minimum Clearances per U.L. Listing:
Top - 6", Front - 24", Sides - 6", Rear - 6", Flue Pipe (Single Wall) - 18", Bottom - 6",
Warm air duct within 3' of furnace (when ducted) - 6"
18” (46 cm) from outer
surface of single-wall flue
tee/pipe in all directions.
6” (15.24 cm) from
blower edge.
24” (61 cm) from
front of cabinet.
6” (15.24 cm) from rear of
cabinet (24” if using rear
air panel discharge).
6” (15.24 cm) from burner.
(72” (183 cm)
recommended for
maintenance access.)
Warm air duct minimum
clearance: 6” (15.24 cm)
within 36” (92 cm) of
furnace.
The unit may be
suspended from the
ceiling.
Minimum Clearances to Combustible Surfaces
6” (15.24 cm) from bottom
panel to combustible
objects.
Note: Repair facility code
(NFPA 88B) requires 96”
(244 cm) from burner to
the floor.
6” (15.24 cm) from top panel.
6
Call 1-615-471-5290 for Technical Support
Содержание EL-140H
Страница 2: ......
Страница 51: ...45 Call 1 615 471 5290 for Technical Support ...
Страница 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Страница 91: ...85 Call 1 615 471 5290 for Technical Support ...
Страница 93: ...87 Call 1 615 471 5290 for Technical Support ...
Страница 94: ...88 Call 1 615 471 5290 for Technical Support ...
Страница 95: ...89 Call 1 615 471 5290 for Technical Support ...