2.2 Tools Required
Below is a recommended list of tools and equipment that may be used to aid in the installation
of EnergyLogic furnaces. This is a minimum list for a Tank-Mount system. Additional tools and
equipment are required for other mounting methods.
Common Tools and Equipment
•
5/16” Combination Wrench
•
Flat Blade Screwdriver
•
3/8” Combination Wrench
•
¼” Hex Wrench or Driver
•
7/16” Combination Wrench
•
Wire cutter to remove tie
straps.
•
1/2” Combination Wrench
•
Forklift or other lift device.
•
9/16” Combination Wrench
•
Safety ladder or man lift.
•
3/4” Combination Wrench
•
(Tools required for flue kit
installation)
•
1-3/8” Combination Wrench
2.3 Furnace Placement Guide
It is important to plan the furnace and tank placement, wiring, piping and flue prior to
installation.
Electrical Wiring
- Will the layout of your building allow safe routing and installation of
electrical wiring to the furnace? Check your local building codes. The EnergyLogic furnace
requires 115 VAC/60 Hz power, supplied through a dedicated, hard wired, circuit breaker – 25
Amp maximum. Use copper conductors only.
Electricity is very dangerous.
Wiring must be installed by a qualified electrician. In the U.S., consult the National Electric
Code (NEC) and local building codes for additional requirements. In Canada, consult the
Canadian Electrical Code, Part I.
Flue Pipe
-
Is ceiling/roof or wall location suitable for a flue pipe to pass through? Are any
obstacles or flammable materials present at interior or exterior locations? Check your roof
warranty about penetration for the flue pipe. Check your local building and fire codes.
Combustion and Make Up Air Requirements
– It is necessary to ensure that adequate air
for safe combustion is provided for oil-burning appliances and equipment. Refer to NFPA 31,
chapter 5 for requirements based on the total input BTU rating of all appliances in the space. In
Canada, reference CSA Standard B139/CGA B149.
Tanks
- The oil tank is to be vented to the outside of the building. Oil
temperature should be maintained at 50°F (10°C) and above. Tank shall
be at least 5 feet away from any source of heat and should not obstruct
service meters, electrical panels, or shut off valves. Check building,
environmental and fire codes for containment and other restrictions.
8
Call 1-615-471-5290 for Technical Support
Содержание EL-140H
Страница 2: ......
Страница 51: ...45 Call 1 615 471 5290 for Technical Support ...
Страница 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Страница 91: ...85 Call 1 615 471 5290 for Technical Support ...
Страница 93: ...87 Call 1 615 471 5290 for Technical Support ...
Страница 94: ...88 Call 1 615 471 5290 for Technical Support ...
Страница 95: ...89 Call 1 615 471 5290 for Technical Support ...