2. Installation Considerations
EnergyLogic furnaces are designed to operate reliably over a wide range of conditions.
However, it is important to read this section before installation to prevent unnecessary work or
problems.
2.1 Technical Guidelines
1.
All components of your furnace are factory-tested to ensure proper operation. Do not
tamper with controls.
2.
Pre-assembled fittings are sealed with thread-locker sealant and do not require
additional tightening.
3.
Always supply power through a dedicated, hard-wired (copper only), 115VAC/60Hz
circuit with a 25 Amp maximum breaker. Check local codes.
4.
Do not use the provided thread-locker sealant on flare fittings. Use the provided
sealant on all NPT threaded connections only.
5.
Do not use Teflon tape on any connections. Loose strands may block small orifices,
affecting unit operation or may damage components.
6.
Route all fuel lines inside building to prevent exposure to cold weather. If this is not
practical, call EnergyLogic for application support.
7.
Locate furnace and tank in a dry area above 50°F (10°C) at all times.
8.
If not installing the pump to an EnergyLogic Tank, mount it according to guidelines in
the EnergyLogic Top Suction Kit packaging instructions.
9.
Do not kink copper tubing. Route tubing as straight and vertical as possible (no loops)
to avoid air pockets.
10. Remember to remove the blower shipping strap prior to installation.
11. Maximize vertical run of flue, and minimize horizontal run. Allow access for clean-out.
12. Mount the wall thermostat to an interior wall. Do not allow it to hang by the wiring
harness. Do not mount it to the furnace cabinet.
13. Do not allow your tank to run out of fuel. If the tank runs out of fuel, air and
contamination will be introduced into the fuel delivery system. An EnergyLogic low-
level cut off switch is recommended to prevent low fuel operation.
14. Never use compression fittings for tubing connections, as they will leak and cause the
burner to shut down.
15. Care should be taken not to over-tighten or cross thread brass fittings.
16. Applying a thin film of anti-seize compound to cabinet side of burner gasket may
reduce gasket sticking to cabinet when swinging burner open.
17. Another source of heat is recommended for periods when the furnace may be off-line
for maintenance or for any other reason.
7
Call 1-615-471-5290 for Technical Support
Содержание EL-140H
Страница 2: ......
Страница 51: ...45 Call 1 615 471 5290 for Technical Support ...
Страница 90: ...10 2 Carlin 50200E Primary Control 84 Call 1 615 471 5290 for Technical Support ...
Страница 91: ...85 Call 1 615 471 5290 for Technical Support ...
Страница 93: ...87 Call 1 615 471 5290 for Technical Support ...
Страница 94: ...88 Call 1 615 471 5290 for Technical Support ...
Страница 95: ...89 Call 1 615 471 5290 for Technical Support ...