78
ESE 1408 DBG ES DIN
Status at: May 2015
Name
Value
Unit
Setting up height above sea
level
< 100
[m]
Temperature
< 25
[°C]
Relative air humidity
< 30
[%]
Table 8.1: Reference conditions Output of the generators
Power reduction
for each addi-
tional
Unit
1 %
100
[m]
4 %
10
[°C]
Table 8.2: Generator power reduction dependent on ambient conditions
Line
max. line length
Unit
HO 7 RN-F or an equivalent 1.5
mm
2
60
[m]
HO 7 RN-F or an equivalent 2.5
mm
2
100
[m]
Table 8.3: Maximum line length of the distribution network as a function of
the cable cross-section
To observe the switching off conditions for a second
failure there is a general limitation required of an overall
length of 100 m. Larger dimensioning of the distribution
network is only to be undertaken by a qualified electri-
cian or trained personnel. One should ensure in all cas-
es that the impedance of the fault loop does not exceed
1.5Ohm.
Ambient conditions
Reduced power
Distribution network