50
ESE 1408 DBG ES DIN
Status at: May 2015
5 Using special fittings / accessories
5.1 TN-S system with 30mA FI protection
switch
The 30mA FI protection switch option can only be supplied
by the factory.
The FI circuit breaker (RCD) is a protective measure against
dangerous body currents according to DIN VDE 0100-551.
1.
The assembly's earthing connection clamps must be
connected to the earthing spike by at least 16mm² of
earthing cable (green/yellow). The spike must be driven
into the ground. BG Bau recommends an earthing re-
sistance of ≤ 50Ω (see BGI 867).
2.
Alternatively, a proper earthing device conforming to
VDE 0100-540 can be used (such as the main earthing
line in buildings).
Fig. 4.8: FI protection switch
Earthing requirements: