BA00213C/07/EN/14.13
71228814

Operating Instructions

PROFIBUS-PA/-DP

Field Communication for Smartec S CLD132/134

8

Содержание Smartec S CLD132

Страница 1: ...Products Solutions Services BA00213C 07 EN 14 13 71228814 Operating Instructions PROFIBUS PA DP Field Communication for Smartec S CLD132 134 8 ...

Страница 2: ...serious injury WARNING Cause consequences Consequences if safety message is not heeded Corrective action This symbol alerts you to a dangerous situation Failure to avoid the situation can result in a fatal or serious injury CAUTION Cause consequences Consequences if safety message is not heeded Corrective action This symbol alerts you to a dangerous situation Failure to avoid this situation can re...

Страница 3: ...onnection check 10 4 Operability 11 4 1 Display and operating elements 11 4 2 Operation via FieldCare 11 5 System integration 12 5 1 Block model of PROFIBUS PA DP 12 5 2 Cyclical data exchange Data_Exchange 18 5 3 Acyclical data exchange 22 6 Commissioning 30 6 1 Function check 30 6 2 Setting of device address 30 6 3 Device data and type files 32 7 Diagnostics and troubleshooting 35 8 Accessories ...

Страница 4: ...purposes and permits connection of several measuring instruments to a bus line The transmission method according to IEC 1158 2 guarantees safe signal transmission The PROFIBUS PA interface permits operation of the instrument from the PC via FieldCare Plant Asset Management Tool Any other use than the one described here compromises the safety of persons and the entire measuring system and is not pe...

Страница 5: ...ctions Endress Hauser 5 1 5 Product safety The product is designed to meet state of the art safety requirements has been tested and left the factory in a condition in which it is safe to operate Relevant regulations and European standards have been observed ...

Страница 6: ...r either PC with FieldCare or Programmable logic controller PLC a0005890 Fig 1 Measuring systems with PROFIBUS interface 1 PC with PROFIBUS interface 2 PLC 3 Smartec S CLD132 134 PROFIBUS DP compact version 4 Segment coupler 5 Termination 6 Smartec S CLD132 134 PROFIBUS PA compact version 7 Smartec S CLD132 134 PROFIBUS PA separate version with CLS52 54 PROFIBUS PA PROFIBUS DP 1 2 3 4 5 ENDRESS HA...

Страница 7: ...s coupler output and the required bus length For detailed information on function and connection of a PROFIBUS system please refer to Technical Information TI00260F 00 en 2 2 Post installation check After installation check the transmitter for damage Check whether the transmitter is protected against moisture and direct sunlight e g by the weather protection cover ...

Страница 8: ... the power source before you remove the cover frame 2 Remove the cover frame from the terminal blocks To do this introduce a screwdriver in the recess A according to å 2 and push the tab inward B 3 Thread the cables through the open cable glands into the connection compartment 4 Cable connection for PA devices Connect the cable wires of the bus cable in accordance with å 3 to the terminal block Mi...

Страница 9: ...1 GND 2 Power supply 5 V for bus termination 3 B RxD TxD P 4 A RxD TxD N Y Next PROFIBUS device Z Bus termination 99 98 67 68 69 85 86 93 94 81 82 99 98 67 68 69 85 86 93 94 81 82 M12 PE PE PA PA PA BK BK PA a0012694 Fig 4 Insert the screwdriver opens the terminal a0012695 Fig 5 Insert the cable until the limit stop a0012696 Fig 6 Remove the screwdriver closes the terminal ...

Страница 10: ...ach end Each PROFIBUS DP segment must be terminated with an active bus termination on each end 3 2 Post connection check After the electrical connection carry out the following checks Device condition and specifications Notes Are the transmitter and cables damaged on the outside Visual inspection Electrical connection Notes Are the mounted cables strain relieved Cable run without loops and cross o...

Страница 11: ...ure all intelligent field devices in your plant and supports you in managing them By using status information it also provides a simple but effective means of checking their health Supports HART and PROFIBUS Operates all Endress Hauser devices Integrates third party devices such as actuators I O systems and sensors supporting the FDT standard Ensures full functionality for all devices with DTMs Of...

Страница 12: ...r can process more than one process variable a0005920 en Fig 9 Block model of Smartec S grey profile blocks Sensor Signal processing Manufacturer specific parameters Analyzer Transducer Block 1 Main Meas Value Main Process Value Analog Input Block 1 Main Meas Value Main Process Value Analyzer Transducer Block 2 Temperature Value Temperature Analog Input Block 2 Temperature Value Temperature OUT VA...

Страница 13: ...verwritten 0 Hardware write protection disabled device data can be overwritten Software write protection You can also set software write protection to prevent all parameters from being acyclically overwritten You can do so by making an entry in the WRITE_LOCKING parameter The following entries are permitted 2457 Device data can be overwritten factory setting 0 Device data cannot be overwritten Par...

Страница 14: ...f an Analog Input function block The Analog Input function block receives its input value from the Analyzer Transducer Block The input values are permanently assigned to each Analog Input function block Main measured value Main Process Value Analog Input function block 1 AI 1 Measured temperature value temperature Analog Input function block 2 AI 2 1 all data to PNO default values 2506 transmitter...

Страница 15: ...ng mode you can directly specify the OUT output value and the OUT status The most important functions and parameters of the Analog Input Block are listed below Selecting the operating mode The operating mode is set by means of the MODE_BLK parameter group The Analog Input function block supports the following operating modes AUTO automatic mode MAN manual mode O S out of service Selecting the unit...

Страница 16: ... by means of various parameters of the Analog Input function block 1 Simulating the input of the Analog Input function block The SIMULATION parameter group can be used to specify the input value measured value and status Since the simulation value runs through the entire function block you can check all the parameter settings of the block 2 Simulating the output of the Analog Input function block ...

Страница 17: ...u can set two warning limits and two alarm limits for monitoring your process The status of the measured value and the parameters of the limit value alarms are indicative of the measured value s relative position You also have the option of defining an alarm hysteresis in order to avoid frequent changes of the limit value flags and frequent enabling disabling of alarms The limit values are based o...

Страница 18: ...tch This byte transfers the external hold and the parameter set switch from the PLC to the transmitter Structure of the output data PLC to Smartec S The output data of the PLC for device control have the following structure Index Input Data Data Access Data format Configuration data 0 4 Analog Input Block 1 Main Process Value read Measured value 32 bit floating point number IEEE 754 Status byte 0x...

Страница 19: ...5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 V Z 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 2 1 2 2 2 3 2 4 2 5 2 6 2 7 2 8 2 9 2 10 2 11 2 12 2 13 2 14 2 15 2 16 2 17 2 18 2 19 2 20 2 21 2 22 2 23 S Exponent Mantissa Formula IEEE 754 Value 1 VZ 2 exponent 127 1 Mantissa Example 40 F0 00 00 0 10000001 1110000 00000000 00000000 hexadecimal Byte 1 Byte 2 Byte 3 Byte 4 Value 1 0 2 129 127 1 2 1 2...

Страница 20: ...re of the cyclic data telegram the PROFIBUS master must send the identification FREE_PLACE 00h for the non active blocks Status codes for the OUT parameter of the Analog Input block Status code Device status Meaning Limits 0x00 0x01 0x02 0x03 BAD non specific OK LOW_LIM HIGH_LIM CONST 0x04 0x05 0x06 0x07 BAD configuration error OK LOW_LIM HIGH_LIM CONST 0x0C 0x0D 0x0E 0x0F BAD device failure OK LO...

Страница 21: ...UNCERTAIN sensor calibration OK LOW_LIM HIGH_LIM CONST 0x80 0x83 GOOD ok OK CONST 0x84 0x85 0x86 0x87 GOOD update event OK LOW_LIM HIGH_LIM CONST 0x89 0x8A GOOD active advisory alarm LOW_LIM HIGH_LIM 0x8D 0x8E GOOD active critical alarm LOW_LIM HIGH_LIM Status code Device status Meaning Limits ...

Страница 22: ...ermitted with Smartec S This means that two Class 2 masters can access the transmitter at the same time However you must make certain that they do not both attempt to write to the same data Otherwise the data consistency can no longer be guaranteed When a Class 2 master reads parameters it sends a request telegram to the transmitter specifying the device address the slot index and the expected rec...

Страница 23: ...DESC VAH0 1 162 32 Octetstring r w S STRATEGY 1 163 2 Unsigned16 r w S ALERT_KEY 1 164 1 Unsigned8 r w S TARGET_MODE 1 165 1 Unsigned8 r w S MODE_BLK Actual Permitted Normal 1 166 3 DS 37 Unsigned8 Unsigned8 Unsigned8 r N Cst Cst ALARM_SUM 1 167 8 DS 42 r D Blockparameter SOFTWARE_REVISION 1 168 16 Visible string r Cst HARDWARE_REVISION 1 169 16 Visible string r Cst DEVICE_MAN_ID 1 170 2 Unsigned1...

Страница 24: ... unprotected 1 protected r D DEVICE_CONFIGURATION 1 196 32 Visible string r N INIT_STATE 1 197 1 Unsigned8 1 status before reset 2 run 5 maintenance r w S DEVICE_STATE 1 198 1 Unsigned8 2 run 5 maintenance r w D GLOBAL_STATUS 1 199 2 Unsigned16 r D Gap 1 200 207 E H Parameter ACTUAL_ERROR VAH2 1 208 2 Unsigned16 r D LAST_ERROR VAH3 1 209 2 Unsigned16 r D UPDOWN_FEATURES_SUPP 1 210 1 Octetstring r ...

Страница 25: ...1 2 102 32 Octetstring r w S STRATEGY 1 2 103 2 Unsigned16 r w S ALERT_KEY 1 2 104 1 Unsigned8 r w S TARGET_MODE 1 2 105 1 Unsigned8 r w S MODE_BLK Actual Permitted Normal 1 2 1016 3 DS 37 Unsigned8 Unsigned8 Unsigned8 r N Cst Cst ALARM_SUM 1 2 107 8 DS 42 r D Block parameter COMPONENT_NAME 1 2 108 32 Octetstring r w S PV 1 2 109 12 DS 60 r D PV_UNIT 1 2 110 2 Unsigned16 r w S PV_UNIT_TEXT 1 2 111...

Страница 26: ...1 Unsigned8 r w S MODE_BLK Actual Permitted Normal 1 2 22 3 DS 37 Unsigned8 Unsigned8 Unsigned8 r N Cst Cst ALARM_SUM 1 2 23 8 DS 42 r D BATCH 1 2 24 10 DS 67 r w S Gap 1 2 25 Block parameter OUT 1 2 26 5 DS 33 r D PV_SCALE 1 2 27 8 Float r w S OUT_SCALE 1 2 28 11 DS 36 r w S LIN_TYPE 1 2 29 1 Unsigned8 r w S CHANNEL 1 2 30 2 Unsigned16 r w S PV_FTIME 1 2 32 4 Float r w S FSAFE_TYPE 1 2 33 1 Unsig...

Страница 27: ...r w N Temperature measurement V1H0 3 109 1 Unsigned8 0 fixed 1 Pt 100 2 Pt 1000 3 NTC r w N Process temperature V1H3 3 110 4 Float r w N Cell constant V1H4 3 111 4 Float r w N Installation factor V1H6 3 112 4 Float r w N Calibration temperature V1H8 3 113 4 Float r w N Temperature correction V1H9 3 114 4 Float r w N Contact function V3H0 3 115 1 Unsigned8 0 Alarm function 1 Limit function 2 Limit ...

Страница 28: ...nsigned8 r w N Selection of concentration table elements V5H5 3 132 1 Unsigned8 r w D Conductivity concentration table V5H6 3 133 4 Float r w N Concentration concentration table V5H7 3 134 4 Float r w N Temperature concentration table V5H8 3 135 4 Float r w N Status concentration table V5H9 3 136 1 Unsigned8 0 Ok 1 Service 2 Processing 3 Invalid r D Current alpha table V6H0 3 137 1 Unsigned8 1 Use...

Страница 29: ...arm delay V8H3 3 147 2 Unsigned16 r w N Diagnostic code selection V8H4 3 148 1 Unsigned8 r w D Alarm status V8H5 3 149 1 Unsigned8 0 no 1 yes r D Alarm relay V8H6 3 150 1 Unsigned8 0 no 1 yes r w N Security locking V8H9 3 151 2 Unsigned16 22 not protected 9998 loc op disabl 9999 hardware prot r w N Hold function V9H0 3 152 1 Unsigned8 r w N Hold dwell period V9H1 3 153 2 Unsigned16 r w N MRS versi...

Страница 30: ...ces have the address 126 on leaving the factory You can use this address for device function checking and for connection to a PROFIBUS PA network You must change this address to be able to integrate additional devices The device address can be set via Local operation PROFIBUS communication DIL switch in the device Valid device addresses are in the range 0 to 125 Each address may only be given once...

Страница 31: ...t the device address 1 Loosen the four Phillips screws and remove the housing cover The DIL switch is situated on the electronic module above the display 2 Set the device address from 0 to 126 at switches 1 to 7 Example 18 2 16 switch 2 and switch 5 ON 3 Set switch 8 to OFF 4 Close the housing cover a0005212 Fig 14 Hardware setting of the device address example address 18 Set the device address vi...

Страница 32: ...you Manufacturer specific GSD with Profile 3 0 functionality This GSD guarantees the unlimited functionality of the field device Device specific process parameters and functions are therefore available Manufacturer specific GSD with Profile 2 0 functionality This GSD guarantees downward compatibility to the Smartec S transmitter with Profile 2 0 functionality With this you can use the Smartec S tr...

Страница 33: ...vice specific bitmaps can be found in the BMP and DIB subdirectories GSD folder Info folder Information relating to the transmitter and any dependencies in the device software Please read the information in the Info folder carefully before configuring Name of device ID no GSD Ident_Number_ Selector Bitmaps Smartec S only Profile 3 0 functionality Smartec S PA 9750 Hex PA139750 gsd 0 PA_9750n bmp S...

Страница 34: ...300 400 PLC with configuration software Siemens STEP 7 Copy the GSD files to the subdirectory siemens step7 s7data gsd The bitmap files also belong to the GSDs These bitmap files are used to display the measuring points in image form Load the bitmap files to the directory siemens step7 s7data nsbmp If you are using configuration software other than that referred to above ask your PLC manufacturer ...

Страница 35: ...A_MEASUREMENT 00 01 00 00 00 00 BAD configuration error 04 Failure E045 Calibration aborted 20 00 00 80 DIA_MEASUREMENT 00 02 00 00 00 00 BAD configuration error 04 Failure E049 Installation factor exceeded 20 00 00 80 DIA_MEASUREMENT 00 04 00 00 00 00 BAD configuration error 04 Failure E050 Installation factor undershot 00 20 00 80 DIA_MAINTENANCE 00 08 00 00 00 00 BAD configuration error 5C Fail...

Страница 36: ... 00 80 Failure E116 Download error 00 04 00 80 DIA_CONF_INVAL 00 00 08 00 00 00 BAD configuration error 04 Maint E150 Distance of the temperature values or value table too low 00 20 00 80 DIA_MAINTENANCE 00 00 00 01 00 00 UNCERTAIN configuration error 5C Failure E152 Live Check alarm PCS 20 00 00 80 DIA_MEASUREMENT 00 00 00 02 00 00 BAD sensor failure 10 NAMUR class Error no Description DIAGNOSIS ...

Страница 37: ...M 12 plug with socket E H PROFIBUS PA PROFIBUS DP ENDRESS HAUSER SMARTEC S ENDRESS HAUSER SMARTEC S ALARM CAL E ENDRESS HAUSER SMARTEC S ENDRESS HAUSER SMARTEC S ALARM CAL E ENDRESS HAUSER SMARTEC S ENDRESS HAUSER SMARTEC S ALARM CAL E 1 2 3 4 5 6 7 8 9 8 5 1 PLC configuration tools 6 Smartec S separate mounting 2 GSD 7 M12 plug 3 PLC 8 Fieldbus connection box 4 Segment coupler 9 Bus termination b...

Страница 38: ...1502183 Ready made cable with M12 plug and M12 coupling of hard PU and nickel plated brass threads IP 67 screen connected to the thread PVC sheath twisted and screened conductor pair 2 18 AWG temperature range 40 to 70 C 40 to 178 F Cable length 1 m 3 28 ft order no 52001025 Cable length 2 m 6 56 ft order no 52001040 Cable length 5 m 16 41 ft order no 52001041 Cable length 10 m 32 81 ft order no 5...

Страница 39: ...file version 3 0 Display error code Physical layer IEC 61158 2 MBP Manchester bus coded Bus voltage 9 to 32 V Bus error consumption 10 mA 1 mA Errorcurrentconsumption IFDE 0 mA 9 2 Output PROFIBUS DP Output signal PROFIBUS DP acc to EN 50170 vol 2 profile version 3 0 DP function Slave Transmission rate 9 6 kbps 19 2 kbps 45 45 kbps 93 75 kbps 187 5 kbps 500 kbps 1 5 Mbps Signal coding NRZ code Res...

Страница 40: ...ation Via PROFIBUS with FieldCare Bus address Set via DIL switch or via operating menu or via Set_Slave_Adr service Communication interface PROFIBUS PA DP 9 4 Standards and guidelines PROFIBUS EN 50170 vol 2 PROFIBUS DP EN 50170 vol 2 RS 485 PNO guidelines for PROFIBUS DP PROFIBUS PA EN 50170 vol 2 RS 485 PNO guidelines for PROFIBUS PA ...

Страница 41: ...Smartec S CLD132 134 PROFIBUS PA DP Technical data Endress Hauser 41 ...

Страница 42: ...cal connection 8 Electromagnetic compatibility 4 F FieldCare 11 Floating point number 19 Function check 30 I IEEE floating point number 19 Input Daten 18 O Operation 11 FieldCare 11 Operational safety 4 Output DP 39 PA 39 P Post connection check 10 Post installation check 7 Product safety 5 R Requirements for the personnel 4 S Safety instructions 4 Set device address 30 Slot index tables 23 Standa...

Страница 43: ...Smartec S CLD132 134 PROFIBUS PA DP Endress Hauser 43 ...

Страница 44: ...www addresses endress com 71228814 ...