Electrical connection
Proline Promass A 100
24
Hauser
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shielding
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
Modbus RS485
The EIA/TIA-485 standard specifies two types of cable (A and B) for the bus line which
can be used for every transmission rate. Cable type A is recommended.
Cable type
A
Characteristic impedance
135 to 165 Ωat a measuring frequency of 3 to 20 MHz
Cable capacitance
<30 pF/m
Wire cross-section
>0.34 mm
2
(22 AWG)
Cable type
Twisted pairs
Loop resistance
≤110 Ω/km
Signal damping
Max. 9 dB over the entire length of the cable cross-section
Shielding
Copper braided shielding or braided shielding with foil shield. When grounding
the cable shield, observe the grounding concept of the plant.
EtherNet/IP
The standard ANSI/TIA/EIA-568-B.2 Annex specifies CAT 5 as the minimum category
for a cable used for EtherNet/IP. CAT 5e and CAT 6 are recommended.
For more information on planning and installing EtherNet/IP networks, please
refer to the "Media Planning and Installation Manual. EtherNet/IP" of the ODVA
Organization.
Connecting cable between Safety Barrier Promass 100 and measuring device
Cable type
Shielded twisted-pair cable with 2x2 wires. When grounding the cable shield,
observe the grounding concept of the plant.
Maximum cable resistance
2.5 Ω, one side
‣
Comply with the maximum cable resistance specifications to ensure the
operational reliability of the measuring device.
Wire cross-section
Maximum cable length
[mm
2
]
[AWG]
[m]
[ft]
0.5
20
70
230
0.75
18
100
328
1.0
17
100
328