Proline Promass A 100
Commissioning
Hauser
49
10.3
Configuring the device address via software
Applies only to device version with EtherNet/IP communication type
Software addressing is carried out in the
Communication
submenu.
Navigation path
"Setup" menu → Communication
When delivered, the measuring device has the following factory settings:
Ethernet network and Web server
IP address
192.168.1.212
Subnet mask
255.255.255.0
Default gateway
192.168.1.212
• If hardware addressing is active, software addressing is disabled.
• If a switch is changed to the "ON" position, then the first three octets of the
software address are retained.
If the IP address of the device is not known, the device address currently
configured can be read out: Operating Instructions for the device
10.4
Configuring the measuring device
The
Setup
menu with its submenus is used for fast commissioning of the measuring
device. The submenus contain all the parameters required for configuration, such as
parameters for measurement or communication.
Submenu
Meaning
System units
Configuring the units for all measured values
Medium selection
Defining the medium
Communication
Configuration of the digital communication interface
Low flow cut off
Configuring the low flow cut off
Partial filled pipe detection
Configuring the monitoring of partial and empty pipe
detection
10.5
Defining the tag name
To enable fast identification of the measuring point within the system, you can enter a
unique designation using the
"Device tag" parameter
and thus change the factory
setting.
Navigation
"Setup" menu