Proline Promass A 100
Operation options
Hauser
41
8.2.2
Prerequisites
Hardware
Connecting cable
Standard Ethernet cable with RJ45 connector
Computer
RJ45 interface
Measuring device
Web server must be enabled; factory setting: ON
Software of the computer
Web browsers supported
• Microsoft Internet Explorer 7.x, 8.x, 9.x
• Mozilla Firefox 4.x, 5.x, 8.x
• Google chrome 15.x
Recommended operating systems
• Windows XP
• Windows 7
User rights for TCP/IP settings
Admin rights required (e.g. for changing the IP address, subnet mask)
Computer configuration
• JavaScript is enabled
• If JavaScript cannot be enabled, enter http://XXX.XXX.X.XXX/
basic.html in the address line of the Web browser, e.g. http://
192.168.1.212/basic.html. A fully functional but simplified version
of the operating menu structure starts in the Web browser.
8.2.3
Establishing a connection
Configuring the Internet protocol of the computer
The following information refers to the default Ethernet settings of the device.
IP address of the device: 192.168.1.212 (factory setting)
IP address
192.168.1.XXX; for XXX all numerical values except: 0, 212 and 255 → e.g.
192.168.1.213
Subnet mask
255.255.255.0
Default gateway
192.168.1.212 or 0.0.0.0
1. Switch on the measuring device and connect to the computer via the cable
2. Configure the properties of the Internet protocol (TCP/IP) as defined in the table
above.
Starting the Web browser
1. Enter the IP address of the Web server in the address line of the Web browser:
192.168.1.212
2. If the IP address of the measuring device is known, enter the defined device
address in the address line of the Web browser. If it is unknown, set DIP switch
Содержание Proline Promass A 100
Страница 13: ...Proline Promass A 100 Storage and transport Endress Hauser 13 A0015604 A0015605...
Страница 54: ......
Страница 55: ......
Страница 56: ...www addresses endress com...