Proline Promass 80S, 83S
6
Hauser
Output
Output signal
Promass 80
Current output:
Active/passive selectable, galvanically isolated, time constant selectable (0.05 to 100 s), full scale
value selectable, temperature coefficient: typically 0.005% o.r./°C, resolution: 0.5
μ
A
• Active: 0/4 to 20 mA, R
L
< 700
Ω
(for HART: R
L
≥
250
Ω
)
• Passive: 4 to 20 mA; supply voltage U
S
18 to 30 V DC; R
i
≥
150
Ω
Pulse/frequency output:
Passive, open collector, 30 V DC, 250 mA, galvanically isolated.
• Frequency output: full scale frequency 2 to 1000 Hz (f
max
= 1250 Hz), on/off ratio 1:1, pulse width
max. 2 s
• Pulse output: pulse value and pulse polarity selectable, pulse width configurable (0.5 to 2000 ms)
PROFIBUS PA interface:
• PROFIBUS PA in accordance with EN 50170 Volume 2, IEC 61158-2 (MBP), galvanically isolated
• Profile Version 3.0
• Current consumption = 11 mA
• Permitted supply voltage: 9 to 32 V
• Bus connection with integrated reverse polarity protection
• Error current FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: 31.25 kBit/s
• Signal encoding: Manchester II
• Function blocks: 4 × Analog Input, 2 × Totalizer
• Output data: Mass flow, Volume flow, Density, Temperature, Totalizer
• Input data: Positive zero return (ON/OFF), Zero point adjustment, Measuring mode, Totalizer
control
• Bus address can be configured via miniature switches or via the local display (optional)
Promass 83
Current output:
Active/passive selectable, galvanically isolated, time constant selectable (0.05 to 100 s), full scale
value selectable, temperature coefficient: typically 0.005% o.r./°C, resolution: 0.5
μ
A
• Active: 0/4 to 20 mA, R
L
< 700
Ω
(for HART: R
L
≥
250
Ω
)
• Passive: 4 to 20 mA; supply voltage U
S
18 to 30 V DC; R
i
≥
150
Ω
Pulse/frequency output:
active/passive selectable, galvanically isolated
• Active: 24 V DC, 25 mA (max. 250 mA during 20 ms), R
L
> 100
Ω
• Passive: open collector, 30 V DC, 250 mA
• Frequency output: full scale frequency 2 to 10000 Hz (f
max
= 12500 Hz), on/off ratio 1:1, pulse width
max. 2 s
• Pulse output: pulse value and pulse polarity selectable, pulse width configurable (0.05 to 2000 ms)
HART protocol
Order code "Power supply; Display", option A, B, C, D, E, F, G, H, X, 7, 8 (HART 5)
• Valid until software: 3.01.XX
Order code "Power supply; Display", option P, Q, R, S, T, U, 4, 5 (HART 7)
• Valid as of software: 3.07.XX
PROFIBUS DP interface:
• PROFIBUS DP in accordance with EN 50170 Volume 2
• Profile Version 3.0
• Data transmission rate: 9.6 kBaud to 12 MBaud
• Automatic data transmission rate recognition
• Signal encoding: NRZ Code
• Function blocks: 6 × Analog Input, 3 × Totalizer