Commissioning
Proline Promag W 400 HART
94
Hauser
Parameter
Prerequisite
Description
Selection / User
entry
Factory setting
Assign limit
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Select process variable for limit
function.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
• Flow velocity
• Conductivity
• Corrected
conductivity
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Temperature
• Electronic
temperature
Volume flow
Assign flow direction check
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Flow direction check
option is selected in the
Switch output function
parameter.
Select process variable for flow
direction monitoring.
• Off
• Volume flow
• Mass flow
• Corrected volume
flow
Volume flow
Assign status
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Status
option is
selected in the
Switch
output function
parameter.
Select device status for switch
output.
• Empty pipe
detection
• Low flow cut off
Empty pipe detection
Switch-on value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-on point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
Switch-off value
• In the
Operating mode
parameter, the
Switch
option is selected.
• In the
Switch output
function
parameter, the
Limit
option is selected.
Enter measured value for the
switch-off point.
Signed floating-point
number
Country-specific:
• 0 l/h
• 0 gal/min (us)
Switch-on delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-on
of status output.
0.0 to 100.0 s
0.0 s
Switch-off delay
• The
Switch
option is
selected in the
Operating
mode
parameter.
• The
Limit
option is selected
in the
Switch output
function
parameter.
Define delay for the switch-off
of status output.
0.0 to 100.0 s
0.0 s
Failure mode
–
Define output behavior in
alarm condition.
• Actual status
• Open
• Closed
Open
Invert output signal
–
Invert the output signal.
• No
• Yes
No
*
Visibility depends on order options or device settings