Proline Promag W 400 HART
Diagnostics and troubleshooting
Hauser
133
Diagnostic
number
Short text
Remedy instructions
Status
signal
[from the
factory]
Diagnostic
behavior
[from the
factory]
Diagnostic of configuration
410
Data transfer
1. Check connection
2. Retry data transfer
F
Alarm
412
Processing download
Download active, please wait
C
Warning
431
Trim 1
Carry out trim
C
Warning
437
Configuration
incompatible
1. Restart device
2. Contact service
F
Alarm
438
Dataset
1. Check data set file
2. Check device configuration
3. Up- and download new
configuration
M
Warning
441
Current output
1. Check process
2. Check current output settings
S
Warning
442
Frequency output 1 to n 1. Check process
2. Check frequency output settings
S
Warning
443
Pulse output 1 to n
1. Check process
2. Check pulse output settings
S
Warning
453
Flow override
Deactivate flow override
C
Warning
484
Failure mode simulation Deactivate simulation
C
Alarm
485
Measured variable
simulation
Deactivate simulation
C
Warning
491
Current output 1
simulation
Deactivate simulation
C
Warning
492
Simulation frequency
output 1 to n
Deactivate simulation frequency
output
C
Warning
493
Simulation pulse output
1 to n
Deactivate simulation pulse output
C
Warning
494
Switch output
simulation 1 to n
Deactivate simulation switch output
C
Warning
495
Diagnostic event
simulation
Deactivate simulation
C
Warning
496
Status input simulation
Deactivate simulation status input
C
Warning
502
CT activation/
deactivation failed
Follow the sequence of the custody
transfer activation/deactivation: First
authorized user login, then set the
DIP switch on the main electonic
module
C
Warning
511
Sensor electronic (ISEM)
faulty
1. Check measuring period and
integration time
2. Check sensor properties
C
Alarm
530
Electrode cleaning is
running
Turn off ECC
C
Warning
531
Empty pipe detection
Execute EPD adjustment
S
Warning
537
Configuration
1. Check IP addresses in network
2. Change IP address
F
Warning
540
Custody transfer mode
failed
1. Deactivate custody transfer mode
2. Reactivate custody transfer mode
F
Alarm
599
Custody transfer
logbook full
1. Deactivate custody transfer mode
2. Clear custody transfer logbook (all
30 entries)
3. Activate custody transfer mode
F
Warning
Содержание Proline Promag W 400 HART
Страница 197: ......