Liquistation CSF48
Operation
Hauser
101
Bottle volume
0 to 100000 ml
Factory setting
30000 ml
Set the bottle volume.
The preset value depends on the bottle
configuration configured. The bottle volume is
always 30 l for individual containers.
In the case of asymmetric distribution, e.g.
6 x 3 l + 2 x 13 l, you can set the bottle volume on
the left and right in the menu items that follow.
Sampling mode
Options
• Time paced CTCV
• Flow paced VTCV
• Time/flow paced CTVV
Factory setting
Time paced CTCV
The following functions depend on the option
selected.
These versions are illustrated individually in the
following section to provide a clearer understanding
of the options.
Time paced CTCV:
A constant sampling volume is taken at steady
intervals.
Flow paced VTCV:
A constant sampling volume is taken at variable
intervals.
Time/flow paced CTVV(only for version with
peristaltic pump):
A variable sampling volume is taken at steady
intervals.
Path: Menu/Setup/Sampling programs
Function
Options
Info