Installation
Levelflex M FMP40 with HART/4...20 mA
24
Hauser
3.6.7
Notes on special mounting situations
Installation at an angle
• For mechanical reasons, rod probes should be
installed as vertically as possible.
• If installing at an angle, the probe length must
be limited, depending on the angle of
installation.
– Up to 1 m = 30°
– Up to 2 m = 10°
– Up to 4 m = 5°
L00-FMP4xIxx-17-00-00-en-048
Separable probes
If there is little mounting space (distance to the
ceiling), it is advisable to use separable rod
probes (
∅
16 mm).
• max. probe length 10 m/394 inch
• max. sideways capacity 20 Nm
• probes are separable several times with the
lengths:
– 500 mm/19.68 inch
– 1000 mm/ 39.37 inch
• torque: 15 Nm
L00-FMP4xxxx-17-00-00-xx-015
Centering of probe end
If the centering disk is mounted at the end of the
probe, it enables a reliable measuring.
See "Ordering structure"
• Centering disk for rod probes:
– d = 45 mm (DN50/2" + DN65/2 1/2")
– d = 75 mm (DN80/3" + DN100/4")
L00-FMP4xxxx-17-00-00-en-068
rope
probe
mount
i
ng ang
l
e
Ø
d
T
i
g
h
ten
i
ng
tor
q
ue
25
N
m
±
5
N
m
Содержание Levelflex M FMP40
Страница 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Страница 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Страница 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Страница 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Страница 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...