Levelflex M FMP40 with HART/4...20 mA
Wiring
Hauser
31
Cable entry
Cable gland: M20x1.5 (only cable entry for Ex d)
Cable entry: G ½ or ½ NPT
Supply voltage
HART, 2-wire
All the following values are the terminal voltages directly at the device:
HART residual ripple, 2-wire: U
ss
≤
200 mV
Power consumption
Min. 60 mW, max. 900 mW
Current consumption
Overvoltage protection
If the measuring device is used for level measurement in flammable liquids which requires the use
of overvoltage protection according to DIN EN 60079-14, standard for test procedures 60060-1
(10 kA, pulse 8/20
μ
s), the following applies:
• The measuring device is used with integrated overvoltage protection with 600V gas tube surge
arrester in the T12 housing, refer to product overview on
or
• This protection is achieved by the use of other appropriate measures (external protection devices
e.g. HAW262Z).
Communication
Current consumption
Terminal voltage
Minimum
Maximum
HART
Standard
4 mA
16 V
36 V
20 mA
7.5 V
36 V
Ex ia
4 mA
16 V
30 V
20 mA
7.5 V
30 V
Ex em
Ex d
4 mA
16 V
30 V
20 mA
11 V
30 V
Fixed current, adjustable e.g. for
solar power operation (measured
value transmitted via HART)
Standard
11 mA
10 V
36 V
Ex ia
11 mA
10 V
30 V
Fixed current for HART Multidrop
mode
Standard
4 mA
1)
1)
Startup current 11 mA.
16 V
36 V
Ex ia
4 mA
1)
16 V
30 V
Communication
Output current
Current consumption/power consumption
HART, 2-wire
3.6 to 22 mA
—
Содержание Levelflex M FMP40
Страница 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Страница 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Страница 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Страница 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Страница 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...