Levelflex M FMP40 with HART/4...20 mA
Installation
Hauser
19
3.5
Special information on interface measurement
Installation in horizontal cylindrical, upright and underground tanks
• Use coax probes or rod probes in the bypass/stilling well. A segmented probe is available as a
special version for longer measuring ranges.
• Any distance from the wall is possible for coax probes or rod probes in the stilling well. In the case
of rod probes, it must be ensured that the probe does not come into contact with the wall.
L00-FMP4xIxx-17-00-00-xx-002
!
Note!
Rope and rod probes can only be freely installed in the tank under certain circumstances - please
contact your Hauser office.
Installation in stilling well or bypass
• A rod probe can be used for pipe diameters
bigger than 40 mm.
• Rod probe installation can take place up to a
diameter size of 100 mm. In the event of
larger diameters, a coax probe is
recommended.
• Welded joints that protrude up to approx.
5 mm inwards do not affect the measurement.
• The pipe may not exhibit any steps in
diameter.
• If a rod probe is used, the probe length must
be 100 mm longer than the lower disposal.
• In the case of rod probes, it must be ensured
that the probe does not come into contact
with the wall. If necessary, use a centering
disk at the end of the probe.
!
Note!
A plastic centering disk has to be used for
interface measurement (see Accessories
L00-FMP4xIxx-17-00-00-xx-003
min.
100
Содержание Levelflex M FMP40
Страница 4: ...Brief overview Levelflex M FMP40 with HART 4 20 mA 4 Endress Hauser...
Страница 87: ...Levelflex M FMP40 with HART 4 20 mA Appendix Endress Hauser 87...
Страница 88: ...Appendix Levelflex M FMP40 with HART 4 20 mA 88 Endress Hauser...
Страница 90: ...Levelflex M FMP40 with HART 4 20 mA Index 90 Endress Hauser...
Страница 92: ...www endress com worldwide BA363F 00 en 03 09 No 71074941 CCS FM SGML 6 0 ProMoDo 71074941...